iNSTaLLaTiON

NOTICE:  This  firebox  in  com-

bination  with  unvented  log 

sets  are  intended  for  use  as 

supplemental  heat.  Use  along 

with  your  primary  heating 

system. Do not install them as 

your primary heat source. If you 

have a central heating system, 

you may run system’s circulat-

ing  blower  while  using  heater. 

This will help circulate the heat 

throughout  the  house.  In  the 

event  of  a  power  outage,  you 

can use unvented logs as your 

primary heat source.

 WARNING: A qualified ser-

vice person must install firebox. 

Follow all local codes.

 WARNING: Never install the 

firebox

•  in a bedroom or bathroom

•  in a recreational vehicle

•  where  curtains,  furniture, 

clothing  or  other  flammable 

objects are less than 42" from 

the front, top or sides of the 

firebox

•  in high traffic areas

•  in windy or drafty areas

  CAUTION:  Log  heaters 

installed  in  this  firebox  create 

warm  air  currents.  These  cur-

rents move heat to wall surfaces 

next to firebox. Installing firebox 

next to vinyl or cloth wall cover-

ings or operating firebox where 

impurities  (such  as,  but  not 

limited to, tobacco smoke, aro-

matic candles, cleaning fluids, 

oil  or  kerosene  lamps,  etc.)  in 

the air exist, may discolor walls 

or cause odors.

IMPORTANT:

 Vent-free  gas  log  heaters  add 

moisture to the air. Although this is beneficial, 

installing  firebox  in  rooms  without  enough 

ventilation air may cause mildew to form from 

too much moisture. See 

Air for Combustion and 

Ventilation

, page 5. 

IMPORTANT:

 Make sure the firebox is level. If 

firebox is not level, log set will not work properly. 

Note:

 Your Vanguard firebox is designed to be 

used in zero clearance installations. Wall or fram

-

ing material can be placed against any exterior 

surface on the rear, sides or top of your firebox, 

except where standoff spacers are integrally at

-

tached. If standoff spacers are attached to your 

firebox,  these  spacers  can  be  placed  directly 

against wall or framing materials. 

Use dimensions shown for rough openings to cre

-

ate the easiest installation (see 

Built-In or Internal 

Wall Firebox Installation

, page 9).

INSTALLATION CLEARANCES

  WARNING:  Maintain  the 

minimum clearances. If you can, 

provide greater clearances from 

floor, ceiling and adjoining wall.

Carefully follow the instructions below. This will 

ensure safe installation.

Minimum Wall and Ceiling Clearances 
(see Figures 5 and 6, page 9)

A.  Clearances  from  the  edge  of  liner  to  any 

combustible wall should not be less than 8" 

(see Figure 5).

B.  Clearances from the top of the firebox opening 

to the ceiling should not be less than 42". 

C.  When the firebox is installed on carpeting or 

other combustible material, other than wood 

flooring, the firebox should be installed on a 

metal or wood panel extending the full width 

and depth of the enclosure.

D.  Clearances from the bottom of firebox to the 

floor is 0".

E.  Clearances from the open end of the firebox 

to the facing wall shall should not be less than 

36".

  CAUTION:  Do  not  install 

the  firebox  directly  on  carpet 

or vinyl. 

Содержание FBPS

Страница 1: ...nce WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch Do not use any phone in your building Immediatelycallyourgassupplierfromaneighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a quali fied installer service agency or the gas supplier WAR...

Страница 2: ...ervice agency or the gas supplier WARNING For use only with decorative type unvented room heaters Do not build a wood fire This firebox has been tested and approved by I A S under their REQ 2 97 for use with any ANS Z21 11 2 approved gas logs This firebox may be installed in an aftermarket perma nently located manufactured mobile home where not prohibited by state or local codes Aftermarket Comple...

Страница 3: ...d and brick liner in place Make sure these parts are in place and screens are closed beforerunningheaterinfirebox The supplied hoods may not be replaced with hoods which may be provided with a log heater Keep the appliance area clear and free from combustible ma terials gasoline and other flam mable vapors and liquids 1 This firebox shall not be installed in a bedroom or bathroom 2 Never install t...

Страница 4: ... located directly above thebricklinerandundertheheat shield See Figure 20 page 15 Product Features Operation This firebox is designed for use with approved ANS Z21 11 2 decorative type unvented room heaters Physical size limitations apply Refer to minimum firebox requirements supplied with log heater The maximum size log this firebox will accept is width of 32 depth of 19 and a height of 17 Produc...

Страница 5: ...ir Read the following instructions to insure proper fresh air for this and other fuel burning appliances in your home Today s homes are built more energy efficient than ever New materials increased insulation and new construction methods help reduce heat loss in homes Home owners weather strip and caulk around windows and doors to keep the cold air out and the warm air in During heating months hom...

Страница 6: ...ating only if there are doorless passageways or ventilation grills between them AIR FOR COMBUSTION AND VENTILATION Continued DETERMINING FRESH AIR FLOW FOR Firebox LOCATION Determining if You Have a Confined or Unconfined Space Use this work sheet to determine if you have a confined or unconfined space Space Includes the room in which you will install heater plus any adjoining rooms with doorless ...

Страница 7: ... two perma nent openings one within 12 of the ceiling and one within 12 of the floor on the wall connecting the two spaces see option 1 Figure 3 You can also remove door into adjoining room see op tion 2 Figure 3 Follow the National Fuel Gas Code ANS Z223 1 NFPA 54 Section 5 3 Air for Combustion and Ventilation for required size of ventilation grills or ducts AIR FOR COMBUSTION AND VENTILATION Con...

Страница 8: ...much moisture See Air for Combustion and Ventilation page 5 IMPORTANT Make sure the firebox is level If firebox is not level log set will not work properly Note Your Vanguard firebox is designed to be used in zero clearance installations Wall or fram ing material can be placed against any exterior surface on the rear sides or top of your firebox except where standoff spacers are integrally at tach...

Страница 9: ...tel Shelf 3 6 9 1 4 Combustible Material 1 1 2 Max Thickness Note All vertical measurements are minimum distances from top of fireplace hood to bottom of mantel shelf These minimum clearances replace any other recommended clearances supplied with your ANS Z21 11 2 approved gas logs Wall board or facing material above firebox may be of combustible material including decorative mantel ornaments or o...

Страница 10: ...s or wood screws through holes in nailing flange see Fig ure 10 Attach firebox to board base through holes in firebox bottom see Figure 10 IMPORTANT When finishing your firebox combustible materials such as wall board gypsum board sheet rock drywall plywood etc may be butted up next to the sides and top of the firebox Combustible materials should never overlap the firebox front facing more than 3 ...

Страница 11: ...accessible from both rooms Check your local codes for ap plicable installation requirements Figure 11 Installing Gas Line and Manual Shutoff Valve Manual Shutoff Valve is Located Under Firebox Floor on Either Side Gas Line Installed Through Access Hole on One Side of Firebox Figure 12 Location of Knockouts for Gas Line Extension Key Shut Off Valve Figure 13 Typical Exterior Wall Gas Shut Off Insta...

Страница 12: ...ting of the gas sup ply piping system at test pressures equal to or less than 1 2 psig 3 5 kPa Figure 15 Locating Electrical Connection and Gas Connection on Either Side of Fireplace Cover Plates Electrical Connection Access Hole Gas Connection Access Hole Hard wiring Firebox Model FBPS can be hard wired to the duplex outlet located inside the firebox bottom if desired This allows the blower acces...

Страница 13: ...rts directed upwards along inner side wall of lower compartment The blower outlets must be installed flush to the outer cabinet for air to flow properly 5 Apply gentle force between hook and loop mounting strips to seat blower 6 Remove control knob and lock nut from blower speed control shaft 7 Place speed control shaft through 3 8 hole provided in right side of lower door panel removed in step 2 ...

Страница 14: ...oth Sides 2 Screws Each End of Hood Corner Post Front Hood Typical Each Side 3 Screws Top Operating Guidelines and Maintenance Instructions When lit for the first time a vent free log heater will emit a slight odor for about an hour or two This is a normal occurrence which is due to the curing of the logs and the burn in of internal paints and lubricants used in the manufacturing process Keep cont...

Страница 15: ...nd to stay away to avoid burnsorclothingignition Young children should be carefully supervised when they are in the same room as the appliance For lighting and operating this vent free firebox please refer to the vent free gas logs manufactur er s instruction manual Parts Not Under Warranty Contact authorized dealers of this product If they can t supply original replacement part s call DESA at 1 8...

Страница 16: ...163 01C 16 Illustrated Parts Breakdown Model FBPS These items are used on both sides of fireplace 8 15 17 17 17 7 1 7 2 7 3 2 17 11 17 17 12 6 16 13 10 5 17 17 15 16 4 16 16 6 16 15 17 17 18 Typ Typ Typ 8 17 17 9 14 16 1 3 ...

Страница 17: ...ng Flange 12 7 1 02013 Side Refractory Brick Liner 1 7 2 02014 Bottom Refractory Brick Liner 1 7 3 02036 Bottom Refractory Brick Liner 1 8 24007 Side Refractory Retainer 2 9 12125 Screen 4 10 26752 Extruded Louver 2 11 26733 Lower Door Panel 2 12 14200 Receptacle 1 13 21171 Access Hole Cover 3 14 12126 Screen 1 15 26771 Extruded Louver End 1 16 11164 Screw 10 x 1 2 zinc PH 24 17 11165 Screw 10 x 5...

Страница 18: ...llation Polished Brass Hood GA6017 For Firebox End GA6054 For Firebox Side Replaces the standard black hood to provide a more formal appearance Note Each kit contains only one hood Two GA6054 kits are required to do both sides of firebox Polished brass louver GBL17 For Firebox End GBL41 For Firebox Side Replaces the standard black louver to provide a more formal appearance Note Each kit contains o...

Страница 19: ...____________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ ______________________________________________________ _________________________________...

Страница 20: ...iring a defective heater will be the responsibility of the owner TO THE FULL EXTENT ALLOWED BY THE LAW OF THE JURISDICTION THAT GOVERNS THE SALE OF THE PRODUCT THIS EXPRESS WARRANTY EXCLUDES ANY AND ALL OTHER EXPRESSED WARRANTIESAND LIMITS THE DURATION OFANYAND ALL IMPLIED WARRANTIES INCLUDING WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE TO FOUR 4 YEARS ON ALL COMPONENTS FROM...

Отзывы: