background image

6

104024

AIR FOR

COMBUSTION

AND

VENTILATION

Continued

DETERMINING AIR FLOW FOR HEATER LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space:

 Includes the room in which you will install heater plus any adjoining rooms with

doorless passageways or ventilation grills between the rooms.

1. Determine the volume of the space (length x width x height).

Length x Width x Height =

___________________

cu. ft. (volume of space)

Example:

Space size

20 ft. (length) x 16 ft. (width) x 8 ft. (ceiling height) =
2560 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the
volume of these rooms to the total volume of the space.

2. Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space

can support.

____________ (volume of space) 

÷

 50 cu. ft. = (maximum Btu/Hr the space can support)

Example: 

2560 cu. ft. (volume of space) 

÷

 50 cu. ft. = 51.2 or 51,200 (maximum

Btu/Hr the space can support)

3. Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free heater

___________________ Btu/Hr

Gas water heater*

___________________ Btu/Hr

Gas furnace

___________________ Btu/Hr

Vented gas heater

___________________ Btu/Hr

Gas fireplace logs

___________________ Btu/Hr

Other gas appliances*

___________________ Btu/Hr

Total

___________________ Btu/Hr

Example:

Gas water heater

40,000

Btu/Hr

Vent-free heater

+

30,000

Btu/Hr

Total

=

70,000

Btu/Hr

* Do not include direct-vent gas appliances. Direct-vent draws combustion air from the
outdoors and vents to the outdoors.

4. Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr

used.

_________________ Btu/Hr (maximum the space can support)
_________________ Btu/Hr (actual amount of Btu/Hr used)

Example:

51,200

Btu/Hr (maximum the space can support)

70,000

Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more
than the maximum Btu/Hr the space can support. You must provide additional fresh air.
Your options are as follows:

A. Rework worksheet, adding the space of an adjoining room. If the extra space provides

an unconfined space, remove door to adjoining room or add ventilation grills between
rooms. See Ventilation Air From Inside Building, page 7.

B. Vent room directly to the outdoors. See Ventilation Air From Outdoors, page 7.
C. Install a lower Btu/Hr heater, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the
space is an unconfined space. You will need no additional fresh air ventilation.

Содержание AMITY SVYD18N

Страница 1: ...tion and operational procedures For assistanceoradditionalinformationcon sultaqualifiedinstaller serviceagency or the gas supplier WARNING This is an unvented gas fired heater It uses air oxygen from...

Страница 2: ...luence of alcohol and those at high altitudes Natural Gas Natural gas is odorless An odor making agent is added to the gas The odor helpsyoudetectagasleak However theodoraddedtothegascanfade Gasmaybep...

Страница 3: ...talterburner flame patterns Ceiling fans can create drafts that alter burner flame patterns Altered burner patterns can cause sooting 9 Do not use a blower insert heat exchanger insert or other access...

Страница 4: ...heat loss out a vent or up a chimney Heat is generated by realistic dancing yellow flames This heaterisdesignedforvent freeoperation Stateandlocalcodesinsomeareasprohibit the use of vent free heaters...

Страница 5: ...struction The air that leaks around doors and windows may provide enough fresh air for combustion and ventilation However in buildings of unusually tight construc tion you must provide additional fres...

Страница 6: ...ter ___________________ Btu Hr Gas fireplace logs ___________________ Btu Hr Other gas appliances ___________________ Btu Hr Total ___________________ Btu Hr Example Gas water heater 40 000 Btu Hr Ven...

Страница 7: ...activate the power vent Figure 2 Ventilation Air from Inside Building VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating...

Страница 8: ...h ventilation air may cause mildew to form from too much moisture See Air for Combustion and Ventilation pages 5 through 7 NOTICE State or local codes may only allow operation of this appliance in a v...

Страница 9: ...Remove plastic bag from stove body 4 Remove back panel from stove see Figure 5 Use an adjustable wrench or a 10 mm socket Remove six 6 bolts and washers Keep bolts and washers to reattach back panel l...

Страница 10: ...on back to attach bottom components to stove body see Figure 6 Rest stove on drop cloth or blanket to avoid scratching stove edges 7 Remove remaining pallet wood attached to bottom of stove body see...

Страница 11: ...a 12mm socket Figure 9 Attaching Stove Legs Bottom Of Stove Unit Leg Bolt Washers INSTALLING Continued 9 Fasten stove bottom to stove with four 4 M6 x 1 25mm bolts Use a flat washer and lock washer w...

Страница 12: ...t The catch bolt has two hex nuts attached to it see Figure 12 The top nut is a bolt stop and the bottom nut is for door leveling adjustment 12 Check general catch bolt alignment with door claw Make f...

Страница 13: ...rol knob extension passes through bottom front opening see Figure 13 INSTALLING Continued 6 Align outside holes on heater base with four 4 mounting holes on the stove bottom see Figure 13 7 Fasten hea...

Страница 14: ...20mm bolts and washers Make sure product identification label is located on the outside lower left hand corner 10 Place freestanding stove in desired position in room Be sure to maintain clearances t...

Страница 15: ...ING Never connect heater to private non utility gas wells This gas is commonly known as wellhead gas The gas regulator for the stove heater is located on the lower right hand side of the stove when vi...

Страница 16: ...after installing or servicing Correct all leaks at once CHECKING GAS CONNECTIONS WARNING ICON G 001 CAUTION Avoid damage to regulator Hold gas regulator with wrench when connecting it to gas piping a...

Страница 17: ...alve see Figure 19 2 Open main gas valve located on or near gas meter 3 Make sure control knob of heater is in the OFF position 4 Check all joints from manual shutoff valve to control valve see Figure...

Страница 18: ...t reach your gas supplier call the fire department C Use only your hand to push in or turn the gas control knob Never use tools If the knob will not push in or turn by hand don t try to repair it call...

Страница 19: ...this heater for the first time after hooking up to gas supply If so the control knob may need to be pressed in for 30 seconds This will allow air to bleed from the gas system 6 With control knob press...

Страница 20: ...access to pilot 3 Depress control knob and light pilot with match 4 Keep control knob pressed in for 30 seconds after lighting pilot After 30 seconds release control knob 5 Place top grate back into...

Страница 21: ...1 CAUTION Never use a wire needle or similar object to clean ODS pilot This can damage ODS pilot unit POSSIBLE CAUSE 1 Ignitor electrode not con nected to ignitor cable 2 Ignitor cable pinched or wet...

Страница 22: ...urn more 7 Replace thermocouple 8 Replace control valve OBSERVED PROBLEM When ignitor button is pressed there is spark at ODS pilot but no ignition ODS pilot lights but flame goes out when control kno...

Страница 23: ...ill stop after a few hours of opera tion 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural gas comp...

Страница 24: ...enough fresh air is available 2 Low line pressure 3 ODS pilot is partially clogged 1 Gas leak See Warning statement at top of page 2 Control valve defective 1 Foreign matter between control valve and...

Страница 25: ...l DESA International s Technical Service Department at 1 800 323 5190 When calling DESA International have ready your name and address model number of your heater how heater was malfunctioning type of...

Страница 26: ...26 104024 ILLUSTRATED PARTS BREAKDOWN SVYD18N 4 20 10 11 12 20 7 20 20 5 6 9 8 15 14 16 18 2 17 13 22 20 18 3 19 2 19 1 19 17 1 21...

Страница 27: ...11 102843 01 Burner Clip 1 12 102980 01 Burner 1 13 102568 07 Control Valve 1 14 098508 01 Valve Retainer Nut 1 15 099393 03 Control Knob 1 16 102445 01 Piezo Ignitor 1 17 099387 08 Pilot Tube 1 18 09...

Страница 28: ...28 104024 ILLUSTRATED PARTS BREAKDOWN SCIVFC SCIVFB SCIVFG SCIVFR 1 2 5 11 7 4 6 5 5 7 1 7 2 5 4 7 3...

Страница 29: ...Green 4 Total Per Stove 1 104175 04 One Leg Burgundy Red 4 Total Per Stove 1 6 104176 01 Leg Leveler Bolt M8 x 1 25 55mm Long 4 Total Per Stove 1 7 104177 01 Hardware Kit 1 7 1 Door Hinge Step Bolt W...

Страница 30: ...not supply these accessories call DESA International s Parts Department at 1 800 972 7879 for referral information You can also write to the address listed on the back page of this manual MANUAL SHUT...

Страница 31: ..._________________________________________ _________________________________________________________________ _________________________________________________________________ __________________________...

Страница 32: ...ll such other costs related to repairing a defective heater will be the responsibility of the owner TOTHEFULLEXTENTALLOWEDBYTHELAWOFTHEJURISDICTIONTHATGOVERNSTHESALEOFTHE PRODUCT THIS EXPRESS WARRANTY...

Отзывы: