LTCA-10/LTCA-40 USER’S MANUAL
37
Press the
[ENTER]
key to start capturing data for the time period selected in
step e
. The
LTC must be manually started to begin switching through the taps.
If the LTC cable is connected, then pressing the
[LTC RAISE]
key when cycling from
lower to higher taps or pressing the
[LTC LOWER]
key when cycling from higher to
lower taps will start capturing data.
The following screen will be displayed indicating that the test is in progress:
h.
When the pre-defined test time has elapsed or the
[STOP]
key is pressed, the “PRINT
TEST RESULTS?” menu will be displayed:
1.
YES
Press the
[1]
key (
YES
) to print the test results on the built-in thermal printer. The
following menu will be displayed:
1.
NORMAL PLOT
Press the
[1]
key (
NORMAL PLOT
) to print a normal plot. The printer will
begin to print. A typical normal (full-scale) plot is shown in figure 11.0.
Continue to step i.
2.
EXPANDED PLOT
To print an expanded plot, press the
[2]
key (
EXPANDED PLOT
).
Continue to step i.
2.
NO
Press the
[2]
key (
NO
) to bypass the printing of the test results.
Continue to step
j.
SELECT PLOT TYPE:
1.
NORMAL PLOT
2.
EXPANDED PLOT
PRINT TEST RESULTS?
1.
YES
2.
NO
RUNNING DYNAMIC
LTC TEST T = 15
R1 = 7.369 m
Ω
“STOP” KEY TO ABORT
* XFMR ENERGIZED! *
Содержание LTCA-10
Страница 17: ...LTCA 10 LTCA 40 USER S MANUAL 17 Figure 5 0 Typical LTCA 40 Connection Diagram 2 Windings...
Страница 18: ...LTCA 10 LTCA 40 USER S MANUAL 18 Figure 6 0 Typical LTCA 40 Connection Diagram 3 Windings...
Страница 28: ...LTCA 10 LTCA 40 USER S MANUAL 28 Figure 9 0 Typical Single Reading Test Report Printout...
Страница 41: ...LTCA 10 LTCA 40 USER S MANUAL 41 Figure 12 0 Sample Dynamic LTC Test Expansion Plot...
Страница 49: ...LTCA 10 LTCA 40 USER S MANUAL 49 Figure 13 0 Typical Test Record Printout...
Страница 51: ...LTCA 10 LTCA 40 USER S MANUAL 51 Figure 14 0 Typical Record Directory Printout...