Accu-Trans
Operating Procedures
11
h)
When either option is selected, the next
window displays with the prompt “KEEP
THIS READING? Go to the next step.
i)
If the KEEP THIS READING prompt is
answered with a YES, the following display
appears.
j)
Go to step
l.
If NO is selected, the next
display is skipped and the second display
following appears.
The TEST SAVED display advises that the
resistance measurement has been saved.
k)
Press ENTER and go to the next step.
“RUN ANOTHER TEST?” message will
appears.
l)
Select NO from “KEEP THIS
RESULTS” will take the user to the “RUN
ANOTHER TEST?” menu.
m)
At the “RUN ANOTHER TEST?”
Menu, the operator may choose to run
another test, by selecting “YES”. Return to
step 6.2.2.a to run test.
n)
If NO is selected (i.e., don’t run another
test) the program returns to the Start-Up.
Menu (section 6.2.1).
6.3
SETUP Menu:
This menu is displayed by again selecting 2
(SETUP) on the Start-UP MENU
a)
Select key 1 to 4. When key #4 (NEXT
PAGE) is selected, More choices for setup
menu are shown (below).
KEEP THIS READING
1.YES
2. NO
TEST SAVED
RUN ANOTHER TEST?
1. YES
2. NO
1. ENTER XFMR DATA
2. REVIEW RECORD
3. RESTORE RECORD
4. NEXT PAGE
1. COMPUTER CONTROL
2. SET TIME
3. ENABLE TEST MODE
4. VOLTAGE REG. TEST