4.2 CONTROLLER ERROR CODES
The controller display panel is used to display error codes in the event of problems with the controller. The four error codes
are listed below.
--
-SENSOR FAILURE
The "--" displayed for the temperature indicates that there is a problem with the sensor. The sensor is open or shorted.
All relays will be de-energized in the event of a sensor failure. If the sensor is damaged, it must be replaced.
EE
-EEPROM FAILURE
The "EE" error code indicates that there is a problem with EEPROM. The values read back from the EEPROM are not
the same as what was written into the EEPROM. This error cannot be field repaired. The controller must be replaced.
-60°F or 270°F (-51°C or 132°C) Blinking
- TEMPERATURE OUT OF RANGE
The temperature display blinks when the sensed temperature is outside of the display range, below -60°F (-51°C) or
above 270°F (132°C). The displayed value remains at the display limit and the controller continues to function unless
an open or shorted condition is detected.
BLINKING RELAY STATUS
This occurs when the Relay Minimum Off Time is active. The (
ñ
) blinks while the relay's minimum off time is active.
DESCRIPTION
CONTROLLER
THERMOWELL
CORD GRIP CONNECTOR
6
'
LONG HEAT TAPE
3/8" CONDUIT STRAIGHT CONECTOR
JUNCTION BOX COVER
3/8" FLEXIBLE CONDUIT
#8-18 x 3/4" SELF TAPPING SCREW
SEAL FITTING FOR CONNECTOR
30
'
ROLL OF INSULATION WRAP
WIRE NUT (yellow)
3/8" 90
O
ELBOW CONDUIT CONNECTOR
TEMPERATURE SENSOR
HEAT CONDUCTIVE COMPOUND
PART NO.
26-7284
29-0325
510-00001
26-0609
26-1068
46-2251
26-0875
28-1283
26-0883
26-0712
26-3383
26-1078
26-7186
26-7189
ITEM NO.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
QTY
1
1
2
1
1
1
6
'
4
4
1
7
1
1
1