Technical description
6 Communication
6.1 Communication ports
VM55.EN005
VAMP 24h support phone +358 (0)20 753 3264
123
6.1.2.
Remote port
Parameters
Parameter
Value
Unit Description
Note
Protocol
None
SPA-bus
ProfibusDP
ModbusSla
ModbusTCPs
IEC-103
ExternalIO
DNP3
Protocol selection for
remote port
-
SPA-bus (slave)
Profibus DB (slave)
Modbus RTU slave
Modbus TCP slave
IEC-60870-5-103 (slave)
Modbus RTU master for
external I/O-modules
DNP 3.0
Set
Msg#
0 ... 2
32
1
Message counter since the
device has restarted or
since last clearing
Clr
Errors
0 ... 2
16
1
Protocol errors since the
device has restarted or
since last clearing
Clr
Tout
0 ... 2
16
1
Timeout errors since the
device has restarted or
since last clearing
Clr
speed/DPS
Display of current
communication
parameters.
Speed = bit/s
D = number of data bits
P = parity: none, even,
odd
S = number of stop bits
1)
Debug
No
Binary
ASCII
Echo to local port
No echo
For binary protocols
For SPA-bus protocol
Set
Set = An editable parameter (password needed)
Clr = Clearing to zero is possible
1) The communication parameters are set in the protocol specific menus. For
the local port command line interface the parameters are set in
configuration menu.