7 Technical data
18
V121/EN M/A017
Voltage tests
Insulation test voltage acc- to IEC 60255-5
2 kV, 50Hz, 1min
Impulse test voltage acc- to IEC 60255-5
5 kV, 1.2/50us, 0.5J
Mechanical tests
Vibration test
2
– 13.2 Hz ±3.5mm
13.2
– 100Hz, ±1.0g
Shock/Bump test acc. to IEC 60255-21-2
20g, 1000 bumps/dir.
Environmental conditions
Specified ambient service temp. range
-35
– +70°C
Transport and storage temp. range
-40
– +70°C
External supply unit
IN
120
– 230V ac, 90 – 250V dc
OUT
24V dc
Alarm relay
Control
24V dc from VAMP121(D)
Rated voltage
250V ac/dc