background image

1.  Do  not  mix  different  refrigerants  together  in  one  tank,or  they  could  not
 

 

     be separated or used.

2.  Before  recovering  the  refrigerant,  the  tank  should  achieve  the  vacuum

    level: -0.1 MPa, which is for purging non-condensable gases. Each tank

      was  full  of  nitrogen  when  it  was  manufactured  in  the  factory,  thus  the

    nitrogen should be evacuated before the first use.

3. The switch should be at "Position 4" before operation. All the valves must

    be closed, the input and output fittings should be covered withprotective

    caps when the unit is not in operation .The air moisture is harmful to the

     recovery result and will shorten the life span of the unit.

4.  A  filter  drier  should  always  be  used  and  should  be  replacedfrequently.

      And  each  type  of  refrigerant  must  have  its  own  filter.  For  the  sake  of

    ensuring the normal operation of the unit, please use the filter specified

    by our company. High quality filter drier will bring high quality services.

5.  Special-caution  is  needed  when  recovering  from  burnt  system,  and  two

     dry filter is needed.
.
6.

    

 The unit has an Internal High Pressure Shut-Off Switch. If the pressure

    inside the system is above 38.5bar, compressor will automatically shut

    off and the power will be off. To restart the compressor, please lower the

      internal  pressure  and  hit  the  Reset  button,  then  turn  on  the  power  to

     restart the compressor.

    When High Pressure Protection is initiated, please please find out the

    cause and deal with it before restarting the unit.
 

Cause of High Pressure Protection and Trouble Shooting:

    

 The input valve of the refrigerant tank is closed——open the valve

 

will

 

      

   
        help

 

solve

 

the

 

problem

.

    

 The connecting hose between the recovery unit and refrigerant tank is 

        stuck——close all the valves and replace the connecting hose.

    

 The temperature of the refrigerant tank is too high, pressure is too    

        high——give it some time to cool down and the pressure will come back  

        to normal.

7.  The  unit  has  an  Internal  Low  Pressure  Shut-Off  Switch  and  Bypas  switch. 

     When the Bypass switch is on automatic, if the pressure inside the system  is 

     below -14±2 inHg(

), the unit will automatically shut off 

     and the Green Alarm Light turns on.If it needs restart the compressor,

 

    pleaseincrease the input pressure above 0.8Kgf/cm  or turn the Bypass    

    switch on manual and then press the start button.     

8.  This  unit  can  be  used  together  with  a  float  level  sensor.  Please  connect 

      the  recovery  unit  and  the  tank  with  the  80%  O.F.P.  Cable(Item  3  in  the 

    PARTS  DIAGRAM).  If  the  liquid  refrigerant  reaches  80%  capacity  of 

    the tank, the recovery unit will automatically shut off and the Red Alarm 

    Light turns on (80% O.F.P.ALARM :item 3 on the PARTS DIAGRAM).Before 

    restart please change a new tank.

9. If the refrigerant tank has no float level sensor, please take the 80%O.F.P 

    Cable off. Otherwise the recovery unit can not started. In this case, an 

    electric scale is required to monitor the recovered refrigerant amount.

.

according

 

to

 

model

2

2

Содержание VRR24L

Страница 1: ...VRR24L E mail sale worldvalue cn http www worldvalue cn...

Страница 2: ...7 8 9 6 10 11 12 14...

Страница 3: ...1 1 the 2 When using an extension cord it should be a minimum 2 0mm AWG and no longer than 7 5 meters or it may cause the voltage drop and damage the compressor 377 1 580...

Страница 4: ...sure Protection is initiated please please find out the cause and deal with it before restarting the unit Cause of High Pressure Protection and Trouble Shooting The input valve of the refrigerant tank...

Страница 5: ...al refrigerant and purged with dry nitrogen 14 Connection hose with check valve is recommended it can prevent refrigerant lose 15 The intake port is equipped with filter screen please wash it frequent...

Страница 6: ...16 FAN FAN COVER POWER SUPPLY CORD BASE AIR COOL CONDENSER O F P CABLE FRONT PANEL PLASTIC COVER COMPONENT CONTROL VALVE COPPER PIPES COMPRESSOR RUNNING CAPACITOR JUNCTION BOX COVER JUNCTION BOX STAR...

Страница 7: ...n 2 for faster recovery 8 Turn the BYPASS switch to AUTO so that the unit will automatically stop when finished Purge operation now 9 When liquid recovery is finished turn the Switch to position 2 for...

Страница 8: ...Open the gas valve and liquid valve of the refrigerant tank 5 Turn the Switch to position 2 to start fast liquid recovery HVAC Syetem O F P cable Scale Tank Vapor Liquid Input Output Filter Liquid va...

Страница 9: ...ther component damage 1 Turn the Switch 2 rounds and point to position 1 and then restart 2 Factory service is needed 1 High Pressure Protection caused by mis operation shuts the unit off like Outlet...

Отзывы: