The equipments must be used within the working temperature and pressure limits laid down for them, otherwise 
they may fail (refer to nameplate and/or IS- Information Sheet). 

Manual  handling  of  products  may  present  a  risk  of  injury.  You  are  advised  to  assess  the  risks  taking  into 
account the task, the individual, the load and the working environment.  

Special care should be taken when harmful fluids (toxic, contaminant, corrosive, etc.) have flowed through the 
valve. Recommended PPE (Personal Protective Equipments) should be use. 

Before starting work ensure that you have suitable tools and/or consumables available. Use only genuine ADCA 
replacement parts. 

Do not remove the marking in the equipment. Serial number and other useful information is there. 

Do not apply the valve for oxygen service, if it hasn’t been specifically manufacture for that purpose. 

During the assembly work, apply protective measures against dirt and all kinds of contamination. 

The equipment should be carefully handled, to prevent any damage in its surfaces. 

Correct installation of the equipment is full responsibility of the contractor 

Valves are designed to be applied in places protected from exposure to weather. 

 

 
 

CLEANING AND PACKING 
 

  This equipment is packed by a proper machine with a special film used by food industry. 

  These equipments are degreased and cleaned ultrasonically. 

  For oxygen application a special cleaning process is applied. 

 
 

TRANSPORT AND STORAGE 
 

 

 

 

Handling and lifting of materials should be made with adequate equipments. 

The valves and equipments should be protected from impacts and forces during transportation and storage. 

We  advice  that  all  the  protective  packing  in  the  valves,  is  kept  during  storage  to  avoid  damage  and 
contamination. The environment should be as clean and dry as possible. 

The valve should be in fully open or closed position to prevent the ball edges to cause damage to the seats. 

The  manufacturer  doesn’t  assume  the  responsibility  of  damaged  equipments  due  to  inappropriate  handling 
during the transportation and storage. 

 

 
 

INSTALLATION 
 

 

 

 

Account for over pressure conditions, according with the local laws or standards.  

Valve mountings such as actuators, handwheels, hoods must not be used with other purpose than the one they 
were built for (e.g. climbing aids or as connecting points for lifting gear) 

For the problems that cannot be solve with the help of this instructions, please contact the supplier or the 
manufacturer. 

 

 
 
 
 

Содержание M3HP

Страница 1: ...tallation and maintenance work must be carried out by trained personnel A supervisor must follow and check all activities For the problems that cannot be solve with the help of this instructions pleas...

Страница 2: ...contractor Valves are designed to be applied in places protected from exposure to weather CLEANING AND PACKING This equipment is packed by a proper machine with a special film used by food industry Th...

Страница 3: ...o weight especially in bigger valves In those cases follow these steps 1 Remove the bolts to separate the valve body from the body connectors 2 Carefully remove the body seals and put them on a clean...

Страница 4: ...tions if necessary MAINTENANCE We recommend the ball valves to be serviced as necessary Ball valves should be checked periodically at least yearly to verify if they are operating correctly if they hav...

Страница 5: ...pression nut 15 4 Remove the belleville spring washers 14 and the spacer 11 5 Remove the stem seals 10 6 Carefully push the stem 5 into the body to remove it 7 Replace all the stem seals and the o rin...

Страница 6: ...Damaged stem seals Remove the lever 12 13 the lock washer 16 and inspect If the spring washers 14 are in good conditions but loosen retighten the compression nut 15 if the spring washers are damaged...