background image

  

 

VAL

S

TEAM

 

ADCA

                       

  

 

We reserve the right to change the design and material of this product without notice.

 

 

 

 

        IMI 1.381 E 05.14

 

 

 

INSTALLATION AND MAINTENANCE INSTRUCTIONS 

FLOAT & THERMOSTATIC STEAM TRAPS 

FLT32 

 

GENERAL 

 

 

These  instructions  must  be  carefully  read  before  any  work  involving  products  supplied  by  VALSTEAM  ADCA 
ENGINEERING S.A. is undertaken. 
 

 

The installation procedure is a critical stage in a life of a steam trap and care should be taken to avoid damage 
to the trap or equipment. 

 

Warning!  

-  At  start  up,  the  presence  of  small  particles  in  the  water  (dirt,  scale,  weld  splatters,  etc)  may  cause  an  imperfect 
closure of the seat. If this occurs, proceed to an accurate cleaning. 
- Do not touch the equipment without appropriate protection during working operation because it may conduct heat 
if the used fluid is at high temperature. 
- Before starting maintenance be sure that the equipment is not pressurized or hot. 
- The equipments must be used  within the  working temperature and pressure  limits laid down for them, otherwise 
they may fail (refer to nameplate and/or IS- Information Sheet). 
- Do not remove the nameplate attached to the equipment. Serial number and other useful information is stamped 
on it. 
 
 

INSTALLATION 

 

 

 

 
-  Before  to  install  remove  plastic  covers  placed  on  flanges  or  connection  ends.  The  equipment  has  an  arrow  or 
Inlet/Outlet designations. Be sure that it will be installed on the appropriate direction. 
- Install the steam trap in the point of the system, where the condensate tends to collect. It must be installed with the 
float lever in horizontal plane, so that it rises and falls vertically. An ADCA strainer should be installed upstream of 
the trap. 

 

 
 

 

 

BODY LIMITING CONDITIONS 

 

FLANGED PN40 / 

ANSI 300 lb * 

FLANGED 

ANSI 150 lb ** 

RELATED  

TEMPERATURE 

ALLOWABLE 

PRESSURE 

ALLOWABLE  

PRESSURE 

37,1 bar 

15,4 bar 

100 ºC 

33,3 bar 

13,8 bar 

200 ºC 

30,4 bar 

12,1 bar 

250 ºC 

27,6 bar 

10,2 bar 

300 ºC 

PMO 

– Max. operating pressure           32 bar; 

TMO 

– Max. operating temperature     250 ºC; 

*Acc. to EN1092-1:2018 ; **Acc. to EN1759-1:2004 
Body limiting conditions PN40 or below, depending on the 
type of connection adopted. Rating PN40 for thread, SW 
and BW. 

FLT32-4,5

4,5 bar

FLT32-10

10 bar

FLT32-14

14 bar

FLT32-21

21 bar

MAX. DIFFERENTIAL PRESSURE