possible, upstairs rooms and loft spaces for signs of escaping smoke indicating a
defective flue. If there is not a definite flow warm the flue for a few minutes and repeat
the smoke pellet test. If there is still no definite flow the flue may need remedial work –
Do not fit the appliance until there is a definite flow through the flue.
6. IGNITION CHECK
Before attempting to install, it is worth checking that
the ignition system performs satisfactorily.
Set the control knob to the off position.
Depress the control knob and rotate it anticlockwise
to the pilot ignition position. A 'click' will be heard
as the integral piezo operates. A spark should be seen
between the electrode and pilot tip
.
If there is no
spark check the following: -
Ensure that the electrode lead is connected to the
terminal at the base of the electrode.
If the above is correct, check for damage to the
electrode lead.
Page 17
INSTALLER GUIDE
Figure 7. Ignition operation