Supply 
pressure
test tapping

Manifold 
pressure
test tapping

Front Face of Control Valve

Pry off
Plastic Cap

Front Face of Control Valve

Pressure Adjustment Screw
behind Cap

Increases Pressure

Decreases Pressure

11.  Replace the main burner with the burner assembly 

supplied with the conversion kit and reassemble 
the module.

12. Lever off  the small 

domed cap covering 
the manifold pressure 
setting screw, on the 
front face of the valve 
cover by using a 
screwdriver or similar.

13. Refi t the module and 

log support to the 
appliance.

14. Fit the aeration shutter 

supplied with the 
kit and set it as per 
diagram.

15. Turn on the gas supply and check for leaks using 

a soap solution. The minimum and maximum gas 

supply pressure are indicated on page 1 and can 
be verifi ed using the inlet supply pressure test 
tapping.

16. Using a small straight blade screwdriver, back off  

the plug screw within the manifold pressure test 
tapping. Fit a manometer to the manifold pressure 
test tapping.

17. Light the appliance and turn up to full fi re. Check 

for leaks downstream of the valve. Adjust the 
manifold pressure setting screw according to 

Specifi cations

 table on page 1. 

18. Turn the appliance off . Remove the manometer 

and tighten the test tapping screw. Refi t the domed 
plug.

19. Fit the data conversion label and signed conversion 

label close to the rating plate. Fit the control 
conversion label near the controls.

20. Re-install fuel bed and check that the appliance 

operates correctly. Refer to main instructions.

Propane Gas Setting

Natural Gas Setting