4.6 Corner Location, Rear Vent
Connection, Horizontal Vent Run Only
See figure 8.
Can be used with either #551DVK standard vent kit or
another terminal cap and accessories. Adapter
#817VAK and 45º elbow will be required. (See venting
options section of this manual.)
4.7Corner Location, Rear Vent Connection,
Vertical Rise, Horizontal Termination
See figure 9.
Can be used with either #551DVK standard vent kit or
another terminal cap and accessories. Adapter
#817VAK, two 90º elbows and pipe lengths will be
required. (See venting options section of this manual).
All the vent pipe dimensional limits are as section 4.4.
4.8 Rear Vent Connection, Vertical Rise,
Through the Roof Termination
See figure 10.
Adapter #817VAK, one 90º vent elbow, pipe lengths, a
vertical vent terminal and roof flashing will be required. Various other ceiling or roof items may be necessary depending on
the particular installation (See venting options section of this manual).
Note
1. The distance from the roof to the lowest terminal discharge opening depends on the roof pitch and must be in accordance
with the manufacturer’s instructions supplied with the termination unit.
2.
The venting system for these appliances is considered to be a
Special Venting System.
The rule in the Installation Code
CAN/CGA–B149 requiring a minimum vent height of 2ft above any portion of a building within 10ft does not,
therefore, apply.
Figure 10 Rear vent connection, through the roof
termination
Figure 9 Corner location, rear vent connection, vertical rise,
horizontal vent run
Figure 8 Corner location, rear vent connection, horizontal vent run