Listen for a snap sound at the gas tap.
Note the time when the sound is heard.
This sound is caused by an electromagnetic valve shutting off the gas supply through
the tap. The valve is located in the body of the tap. The valve should operate
within
60 seconds of the pilot going out.
If the valve does not operate within this time limit
do not allow the appliance to be used until the fault has been corrected.
This monitoring system must not be adjusted, bypassed or put out of
operation.
This monitoring system, or any of its parts, must only be exchanged using
Valor Fires authorised parts.
15. FINAL REVIEW
1.
COMPLETE THE INFORMATION IN THE WARRANTY AND SERVICE SECTION
OF THE OWNER GUIDE (See last pages of the OWNER guide).
2.
Visually inspect the appliance. Clean off any marks incurred during installation.
3.
Advise the customer how to operate the fire.
4.
Explain to the customer that the appliance has a flame failure and spillage
monitoring system. Point out the explanation of this system shown in the owner guide.
Advise that if the fire goes out for any reason, wait at least three minutes before
relighting. Stress that if the monitoring system repeatedly shuts off the fire, the
appliance should be switched off and a specialist should be consulted. Point out that
the lighting instruction details are on a metal plate attached at the bottom of the
appliance behind the firefront and by the control knob.
5.
Advise that the fire may give off a slight odour while new. This is quite normal and it
will disappear after a short period of use.
6.
Advise that any cleaning must only be carried out when the fire is off and cold.
7.
Advise the customer that they should read the Owner guide before operating the
fire and always follow the advice in the section headed “Cleaning your fire”.
8.
Advise the customer that the appliance will operate to its maximum potential if the
flue is primed during the first 20 – 30 minutes of use. To do this, simply turn the
control to its highest setting. This will also burn off any carbon deposits that may have
formed during previous use.
If using the appliance for long periods it is beneficial to change between settings. This
will also help to remove any carbon deposits that may form during use.
9.
Recommend that the appliance should be serviced and the chimney inspected by a
competent person (In the UK a GAS SAFE REGISTER engineer, Outside of the UK a
CORGI or GAS SAFE REGISTER engineer) at least annually.
If the appliance is in premises in the United Kingdom occupied by a tenant, point out
that by law a landlord must have any gas appliance, flue and pipework which is
situated in a tenant’s premises checked for safety at least every 12 months.
Page 33
©
GDC Group Ltd 2014
INSTALLER GUIDE
Содержание 956
Страница 4: ...Page 4 GDC Group Ltd 2014 INSTALLER GUIDE FOR OWNER GUIDE SEE PAGES 38 TO 51 INSTALLER GUIDE...
Страница 7: ...1 IMAGES Page 7 GDC Group Ltd 2014 INSTALLER GUIDE Blenheim Whitsbury Seattle Siva...
Страница 20: ...Page 20 GDC Group Ltd 2014 INSTALLER GUIDE Figure 7 Pack contents continued...
Страница 38: ...Page 38 GDC Group Ltd 2014 OWNER GUIDE OWNER GUIDE FOR WARRANTY AND SERVICE INFORMATION SEE PAGES 48 TO 51...
Страница 52: ...GDC Group Ltd 2014...