INSTALLER’S GUIDE

Page 25

 

Figure 37 Smoke match tube position

maximum setting at the high heat position shown in figure 36. You should feel a check to
the button movement at this position.

6.

 

Slide the control button up past the high heat position to the off (“

O

”) position at the

top of the slide slot. Both pilot and main burner should go out. While cooling the coals
may make some crackling noises. This is quite normal.

13.2

 

Check For Spillage

A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic coals in position

.

1.

 

Close all doors and windows in the room containing the appliance.

2.

 

Light the appliance and set the slide control to the maximum burning position.

3.

 

Leave the appliance on for five minutes.

4.

 

Place the smoke match tube into the

convection box at the right hand side and
immediately below the black top cross
member. Angle it at approximately 45° to
the horizontal.
Insert the tube so that the neck of its
flared end touches the 

inside

 surface of

the edge of the cross member -  See figure
37.
Keeping the neck of flared end in contact
with the edge of the cross member, slide
the tube to the left until you feel it enter
the notch in the edge of the cross
member. Make sure that the tube is pointed upwards at 45º to the horizontal. The
installation is satisfactory if the smoke is drawn into the appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the maximum
setting for a further ten minutes and then repeat the test. If the smoke is still not drawn
into the appliance inspect the sealing to the fireplace surround. If the sealing is
satisfactory but the appliance is installed with the flue restrictor (see section 7 point 8)
remove the restrictor, reseal the appliance and retest. If smoke is still not drawn into the
appliance 

disconnect the appliance and seek expert advice.

5.

 

If the above test is satisfactory open all internal connecting doors, hatches, etc. in the

room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan operating
and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory 

disconnect the appliance and advise the customer of the cause of failure

.

Содержание BG C-1

Страница 1: ...LER Please leave this guide with the owner Manufactured exclusively for British Gas Scottish Gas by Valor Heating For Service Phone 0845 960 5040 Because our policy is one of constant development and...

Страница 2: ...itoring System 26 14 FRONT CASTINGS INSTALLATION 26 15 FINAL REVIEW 27 16 SERVICING PARTS REPLACEMENT 28 16 1 To Remove the Ignition Microswitch 28 16 2 To Remove the Gas Shut Off Microswitch 29 16 3...

Страница 3: ...of at a tipping site licensed for the disposal of industrial waste Protective clothing is not required when handling these articles but we recommend you follow the normal hygiene rules of not smoking...

Страница 4: ...rs to work to recognised standards In the United Kingdom the installation must also be in accordance with All the relevant parts of local regulations All relevant codes of practice The relevant parts...

Страница 5: ...ctional requirements of the current edition of BS715 The dimensions of the flue box must conform to those shown in figure 2 2 2 3 If the fireplace opening is greater than the acceptable dimensions giv...

Страница 6: ...should not be modified The current versions of BS1289 and BS EN 1806 recommend that there should be an air space or insulation between the flue blocks and the plaster because heat transfer may cause...

Страница 7: ...as specified in BS715 The liner must be sealed to the surrounding area above the fireplace opening and to the top of the chimney An approved terminal must be fitted A properly constructed precast con...

Страница 8: ...stible materials or carpets 2 11 The front face of the fireplace should be reasonably flat over the area covered by the convection box top and side flange seals to ensure good sealing These faces shou...

Страница 9: ...quired in the room for this appliance In the Republic of Ireland IE permanent ventilation must comply with the regulations currently in force 2 17 Propane gas appliances must not be installed in a roo...

Страница 10: ...of the appliance is 108mm at either side This clearance is also the minimum recommended at the right side in all installations to allow satisfactory access to the control knob No access clearance from...

Страница 11: ...1 Pair of ceramic side walls 1 Front coal 1 Main coal bed 1 Pack of loose coals containing 4 large 7 medium 2 finger coals 2 Small U seals for convection box side flanges 1 Strip of floor sealing tape...

Страница 12: ...d against a wall with combustible cladding the cladding must be removed from the area covered by the fire front surround see figure 5 We suggest that the actual fire front is used as a template to mar...

Страница 13: ...ion 2 3 of this manual Full instructions for its installation are included with the kit 4 3 Fireplace Flue Pull Close all doors and windows in the room in which the appliance is to be installed After...

Страница 14: ...servicing section in this manual 6 G A S S U P P L Y C O N N E C T I O N A nut and olive are provided for an 8mm pipe inlet connection to the elbow at the bottom front of the appliance The elbow can b...

Страница 15: ...he supply pipe should be left until the appliance is installed in the fireplace For a right side connection the pipe will have to be formed to clear the burner unit mechanism 7 P R E P A R I N G A P P...

Страница 16: ...eal must envelop the pipe If the hole is larger than the pipe seal it with tape Do not pierce the seal unless the supply pipe is to pass through it 7 The appliance is supplied with two fireback spacer...

Страница 17: ...t the fireplace front surround area is sound enough to take the rawlplugs and woodscrews If necessary make sound with a suitable cement 2 Place the convection box centrally in the fireplace in the pos...

Страница 18: ...the fibre plugs supplied Screw the eyebolts into the plugs Make sure that the bolts are secure 4 Place the convection box unit close to the fireplace but allow sufficient access into the fireplace ope...

Страница 19: ...vection box is aligned squarely and the sealing is satisfactory fully tighten the cable retainers 13 If the convection box is not correctly aligned release the tension on the cables by slackening the...

Страница 20: ...the Republic of Ireland check in accordance with the rules in force 9 2 Preliminary Burner Checks Some burner operations can be checked at this stage Checking now will mean that less disassembly will...

Страница 21: ...ed in the servicing section of this guide 9 3 Reference Pressure Check The appliance is pre set to give the correct heat input at the inlet pressure shown in section 1 of this manual No adjustment is...

Страница 22: ...urner compartment See figure 29 1 1 F R O N T S U R R O U N D C O N T R O L L I N K A G E I N S T A L L A T I O N 1 Carefully lift the front surround Do not lift it by the control button Place the fro...

Страница 23: ...the angled ledge at the back of the burner compartment The bottom front recessed edge of the coal base should locate against the step in the burner plaques See figure 31 Installer Note that the small...

Страница 24: ...the vicinity These vapours are quite normal with new appliances They are totally harmless and will disappear after a few hours use 1 Make sure the slider button is at the off position At topmost posi...

Страница 25: ...r slide the tube to the left until you feel it enter the notch in the edge of the cross member Make sure that the tube is pointed upwards at 45 to the horizontal The installation is satisfactory if th...

Страница 26: ...e is located in the body of the tap The valve should operate within 60 seconds of the pilot going out If the valve does not operate within this time limit do not allow the appliance to be used until t...

Страница 27: ...leaning 6 Stress that no extra coals must be added over and above those supplied with the appliance and that any replacements must only be the authorised spares Warn that ignoring this advice could ca...

Страница 28: ...ced items are not broken up but are sealed within a heavy duty polythene bag clearly labelled as RCF waste This is not classified as hazardous waste and may be disposed of at a tipping site licensed f...

Страница 29: ...re front casting 2 Detach the microswitch cover by removing one screw and pulling clear of the location lug See figure 41 3 Loosen the thermocouple nut to free the microswitch leads and pull the leads...

Страница 30: ...of this manual for detailed fitting instructions 16 4 To Replace the Control Slide Unit 1 Remove the front surround See section 16 3 2 Detach the slide unit by removing two screws securing the plasti...

Страница 31: ...erator can now be exchanged 6 Refit in the reverse order 16 8 To Remove the Thermocouple Interrupter Block See figure 49 1 Remove the bottom front and fire front castings and the front surround See se...

Страница 32: ...y Its individual components are not separately replaceable 2 Once removed ensure that the dust cage is cleaned before refitting Make sure that it locates squarely onto the pilot unit without any gaps...

Страница 33: ...properly secured to give a good electrical contact 16 11 To Remove the Gas Flow Rate Controller See figure 52 1 Remove the burner unit See section 16 6 2 Detach the microswitch cover See section 16 1...

Страница 34: ...the base coal The plaques can be then be removed as follows without detaching the front surround or ceramic walls but be careful not to damage the ceramic walls while working inside the firebox 3 Rem...

Страница 35: ...ping strips 9 Refit the coals as described in section 12 of this manual Refit the bottom castings 16 14 To Remove the Appliance from the Fireplace 1 Remove the burner unit See section 16 6 2 Installat...

Страница 36: ...INSTALLER S GUIDE Page 36 1 7 S H O R T L I S T O F S P A R E S...

Страница 37: ...liances 1 540979 Pilot unit For Propane Gas Appliances 544929 G Injector Bray cat 31 size 440 For Natural Gas Appliances 1 569539 Injector Bray cat 15 size 170 For Propane Gas Appliances 581199 H Igni...

Отзывы: