INSTALLER’S GUIDE
Page 25
Figure 37 Smoke match tube position
maximum setting at the high heat position shown in figure 36. You should feel a check to
the button movement at this position.
6.
Slide the control button up past the high heat position to the off (“
O
”) position at the
top of the slide slot. Both pilot and main burner should go out. While cooling the coals
may make some crackling noises. This is quite normal.
13.2
Check For Spillage
A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic coals in position
.
1.
Close all doors and windows in the room containing the appliance.
2.
Light the appliance and set the slide control to the maximum burning position.
3.
Leave the appliance on for five minutes.
4.
Place the smoke match tube into the
convection box at the right hand side and
immediately below the black top cross
member. Angle it at approximately 45° to
the horizontal.
Insert the tube so that the neck of its
flared end touches the
inside
surface of
the edge of the cross member - See figure
37.
Keeping the neck of flared end in contact
with the edge of the cross member, slide
the tube to the left until you feel it enter
the notch in the edge of the cross
member. Make sure that the tube is pointed upwards at 45º to the horizontal. The
installation is satisfactory if the smoke is drawn into the appliance.
If the smoke is not drawn into the appliance leave the appliance alight at the maximum
setting for a further ten minutes and then repeat the test. If the smoke is still not drawn
into the appliance inspect the sealing to the fireplace surround. If the sealing is
satisfactory but the appliance is installed with the flue restrictor (see section 7 point 8)
remove the restrictor, reseal the appliance and retest. If smoke is still not drawn into the
appliance
disconnect the appliance and seek expert advice.
5.
If the above test is satisfactory open all internal connecting doors, hatches, etc. in the
room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan operating
and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation. If the test is not
satisfactory
disconnect the appliance and advise the customer of the cause of failure
.