15. SPILLAGE AND FLAME SUPERVISION CHECKS
15.1 Check for spillage.
1.
Close all doors and windows in the room containing the appliance.
2.
Light the appliance and set the slide control to the maximum burning position.
3.
Leave the appliance on for five minutes.
4.
Place the smoke match into the appliance
canopy (See figure 29).
5.
The installation is satisfactory if the smoke is
drawn into the appliance. If the smoke is not
drawn into the appliance, leave the appliance
alight at the maximum setting for a further ten
minutes and then repeat the test. If smoke is still
not drawn into the appliance, inspect the sealing
to the fireplace surround. If the sealing is
satisfactory but the appliance is installed with the
flue restrictor (See section 8.3), remove the
restrictor, reseal the appliance and retest. If
smoke is still not drawn into the appliance,
disconnect the appliance and seek expert
advice.
6.
If the above test is satisfactory, open all internal connecting doors, hatches, etc., in
the room. Keep all doors and windows that open to the outside of the building closed.
Recheck for spillage as above. If an extractor fan is installed in the same room as the
appliance or a connecting room, check that spillage does not occur with the fan
operating and all doors and other openings between the fan and the appliance open.
If the smoke is drawn into the appliance, continue with the installation.
If the test is
not satisfactory, disconnect the appliance and advise the customer of the cause
of failure.
15.2 Flame supervision and spillage monitoring system.
This pilot unit includes a system that will automatically shut off the gas supply if the
pilot flame goes out or if there is insufficient oxygen due to spillage or poor ventilation.
Check that the system operates properly as follows;
1.
Light the appliance. Set the slide control to the maximum burning position and
leave for one minute.
2.
Set the control to the ‘Low’ burning position. Isolate the gas supply at the inlet ‘T’
connector. The pilot and main burner will go out.
Note the time when the pilot goes
©
Baxi Heating U.K. Limited 2010.
INSTALLER GUIDE
A spillage check must be made before leaving the installed appliance with the
customer. Make this with all the ceramic fuel effect pieces, fascia and firefront
in position
.
Figure 29. Spillage check.