Paneelin osoite
1
Panel address
1
VALLOX DIGIT SE / VKL
CONTROL PANEL
2
4
Control
VALLOX DIGIT SE can be controlled with the control panel coming with the unit (3 at most) and with
optional CO
2
(5 at most) and %RH sensors (2 at most). Fan speeds of the unit can be controlled via
remote monitoring with a voltage or current signal. In case of disturbances, a potential-free relay
contact signal is issued.
With an optional VALLOX LON converter, the whole operation of the unit can be controlled via remote
monitoring.
Week clock control
The week clock in the control panel of the unit can be used to programme the desired fan power
option (1…8) for each hour in the day.
Surface mounting
of control panel
A control panel is mounted
on the wall or on a 1-part
instrument box.
Wiring
Width
90 mm
Height
110 mm
Depth
23 mm
Electronics board of control panel
1 = orange 1
= +
2 = white 1
= –
3 = orange 2
= A
4 = white 2
= B
5 = metal
= signal ground
ca. 21 VDC
}
Cable:
NOMAK 2 x 2 x 0.5 mm
2
+ 0.5 mm
2
NOTE!
Faulty coupling of the (+) wire
destroys the control panel!
21 C
3
10:20
Fan speed can be changed in this display with the + and – buttons
3
Scrolling up
With this button, you can scroll
the displays upward.
Scrolling down
With this button, you can scroll
the displays downward.
Increase button
With this button, you can increase values.
Decrease button
With this button, you can decrease
values.
Start button
With this button, you switch the unit on and off. When the
indicator is lit, the unit is on.
Carbon dioxide adjustment
With this button, you set carbon dioxide adjustment on
and off. When the indicator is lit, the adjustment is on.
Humidity adjustment
With this button, you set humidity adjustment on and off.
When the indicator is lit, the adjustment is on.
Post-heating
With this button, you set post-heating on and off. When
the indicator is lit, post-heating is on. The summer function
is active when the indicator is not lit.
1
2
3
4
5
6
7
8
Fan speed (3).
Supply air temperature (21
°
C).
Post-heating is on.
Time.
Filter guard alert.
Maintenance reminder alert.
Fireplace / booster switch on. The fireplace /
booster switch is activated in this display by
simultaneously pressing down the + and – buttons
for 2 seconds.
Week clock control on.
21 C
10:20
Mounting, removing and wiring of control panel
The control panel is wired straight from the electrical connection box. The control panel can
also be connected in series with a CO
2
sensor or another control panel. (See External
electrical connections on page 7).
Control panel addresses
If two or more control panels are connected to the system, the addresses of the control panels
need to be changed.
E.g. 3 control panels.
• Connect the first control panel to the unit and change its address to 3.
• Connect the second control panel to the unit and change its address to 2.
• Connect the third control panel and make sure that its address is 1.
If control panels have the same address, they go to bus fault state. In this case, remove one of the control panels
and change the address of the other panel. The above mentioned situation can arise in connection with the later
installation of an additional control panel.
Control panel
1 2 3 4 5
+ – A B M