background image

Setting the ventilation profile

As the default factory setting, TTC hoods have the following 

fan control voltages:
Away: 2.5 VDC | At home: 5.0 VDC | Boost: 10.0 VDC

To adjust the control voltage:

Close the damper, turn off the lights, and select  

the At home ventilation profile.
Press the settings button for roughly 3 seconds until the 

setting mode signal light starts to flash. The signal light will 

flash in a series of five flashes to indicate that the 5 VDC 

control voltage is set.
Press the ventilation profile button. The signal light will flash 

in a series of five one quick flashes (5.5 VDC).
Press the ventilation profile button. The signal light will flash 

in a series of six flashes (6.0 VDC).
Press the ventilation profile button. The signal light will flash 

in a series of six one quick flashes (6.5 VDC).  
Keep on pressing until you reach the maximum voltage of 10 

VDC. Next, press the ventilation profile button, which sets 

the control voltage at 2.5 VDC. After this, the voltage will 

increase by 0.5 VDC at a time.
Save the selected control voltage by pressing the settings 

button until the signal lights flash. Saving the fan speed of the 

At home profile also adjusts and saves the fan speed of the 

Away and Boost profiles.
The efficiency of the Away and Boost profiles can also be 

adjusted separately. In this case, adjusting only affects the 

profile that is selected. The profile that is to be adjusted 

needs to be selected when moving to the setting mode.
Alternatively, the control voltage 

can be controlled using a general 

meter.  For that purpose, there are 

probes at the bottom of the filter 

enclosure (see figure).
 

MANU

AL

D

39

32

/1

9.

12

.20

18

Measuring and adjusting 

performance values

 dp 

External electrical connection 

0

10 20 30 40 50 60 70 80 90 100 110 120 130 140 150 160

0

50

100

150

200

250

300

350

400

450

3 = 10.6 V

3 = 7.4 V

2 = 5.3 V

1 = 2.7 V

Adjustment position = control voltage

Pressure difference between exhaust and extract air ducts p

F

, Pa

Exhaust air flow, dm

3

/s

0

10

20

30

40

50

0

20

40

60

80

100

8

6

4

3

2

8

6

4

3

2

Open

Adjustment position of the fan

1 = 2.7 V

Adjustment position of the fan

2 = 5.3 V

Adjustment position 

of the damper

Open

Exhaust air flow

, dm³/s

Pressure difference between exhaust and extract air ducts p

F

, Pa

2 = 2 holes open/damper

3 = 3 holes open/damper

4 = 4 holes open/damper

Boost air flow (with the damper open)

Standard air flow (with the damper closed)

6 = 6 holes open/damper

8 = 8 holes open/damper

Standard ventilation

adjustment position

Standard ventilation 

The volume flow rate of the air inside the 

house extraction fan is measured with 

the damper closed and, where required, 

adjusted based on the static pressure 

loss and the performance scheme of the 

house extraction fan. 
•  Measure the static pressure loss from 

the hole in the damper using the 

measuring tube found in the accessory bag (see figure). 

•  Determine the volume flow rate from the performance scheme 

based on the measured pressure and the number of open holes in 

the damper. 

Adjustment:

•  Cover the required number of holes in the damper with the 

magnetic strip that is delivered with the house extraction fan.

Boost ventilation

The volume flow rate of the air inside 

the house extraction fan is measured 

with the damper open based on 

the static pressure loss and the 

performance scheme. 
•  Measure the static pressure loss 

of the house extraction fan. The 

measuring point must be located 

2 times the duct diameter above 

the outlet collar of the house 

extraction fan (see figure).

•  Determine the volume air flow based on the measured pressure 

and the performance scheme (with the damper open).

ALARM

TACHO

GND

PWM

OPT
+  -

DAMP
IN OUT

MODE
IN OUT

F ALARM

  RS 485
A  B GND

N

L

DAMPER

1    2    3

LIGHT

N    L

FAN

N    L

FAN

IN OUT

PE

Connector

Pot. free contact data 

24 VDC / 5 A

*L

LA

:  damper open – contact closed

 

damper closed – contact open

EXTRA

POSITION OF THE FLAP

*L

LA

CONTACT DATA

GUARD FUNCTION

CONTACT DATA

 dp 

Measuring point,  
min. 2 x duct diameter

Vallox Oy | Myllykyläntie 9-11 | 32200 LOIMAA | FINLAND | www.vallox.com 

Customer S358 10 7732 200 | Afte358 10 7732 270

Отзывы: