background image

10

ELECTRICAL CONNECTIONS

IN

T

E

RNA

L

 E

L

E

C

T

RI

C

A

L

 C

ON

N

E

C

T

ION

LINE: Phase
NEUTRAL: Neutral
SLI: Safety switch phase feed
SNI: Safety switch neutral feed
SLO: Safety switch phase to the circuit board
SNO: Safety switch neutral to the circuit board
SFL: Phase to supply air fan
SFN: Neutral to supply air fan
EFL: Phase to extract air fan
EFN: Neutral to extract air fan
FSO: Fireplace switch feed
FSI: Fireplace switch output
AHL: Post-heating phase
AHN: Post-heating neutral
PHL: Additional heater phase
PHN: Additional heater neutral
BL: Damper motor phase A
BL1: Damper motor phase B
BN: Damper motor neutral
E/I: Error relay feed
E/O: Error relay output

Freezing level adjustment

Fireplace switch

M

1

2

3

Programming connector

Safety / door switch

Belimo damper 
motor 230 VAC

VAK

remote 

monitoring

E/I

E/O

When remote monitoring is used
Leave the signal LED of the external 
control panel or cooker hood 
disconnected.
Also disconnect the short circuit link 
between connectors 3 and 5 
from the female side of the control 
panel connector.

Post-heating control

PWM level adjustment

4

5

6

Protective earth to a separate block

7

8

9

1

Supply 
air fan

2

3

Extract 
air fan

4

5

LINE

NEUTRAL

SLI
SNI
SLO
SNO
SFL

Extract air NTC

Outdoor air NTC

Supply air to the apartment NTC

Exhaust air NTC

Supply air from the cell NTC

SFN
EFL
EFN
FSO

FSI

AHL
AHN
PHL
PHN

230V 50 Hz

BL1

BL

BN
E/I
E/O

9. GND / -
8. Supply fan PWM
7. Supply fan tacho
6. GND / -
5. Extract fan PWM
4. Extract fan tacho
3. GND / -
2. 11,4 VDC / +
1. Control signal S

1

DIP Switch

Up

Down 

1. Post-heating

Electric

VKL

2. Additional heating Electric

MLV

3. Type of the unit

Bypass

Supply fan stop

4. Extra 

An external 0-10VDC voltage supply can be 
connected to the S and GND signals
of the control signal for fan control.

234

DIP switch

ERROR RELAY 
(potential-free)

*Fan neutral to FSI when 
the fireplace switch is used

LED

*Without the fireplace switch, the fan neutral is connected to EFN
With the fireplace switch, the fan neutral is moved to FSI

1

2 3 4

LED

-

+

S

1 2 3 4 5

1 2 3 4 5

Error relay 

90 °C

130 °C

R1

T1

T2

Electric 
post-heating 
radiator 1500 W

70

3

4

8

0

0A

  

Содержание A3740

Страница 1: ...Manual MANUAL Ventilation unit Document D4686 Valid from 31 08 2020 Updated 20 01 2021 Model Vallox 101 MC R Vallox 101 MC L Type A3740...

Страница 2: ...o not ensure safe operation of the unit Such persons can use the unit under supervision or by following the instructions of someone who is responsible for their safety 12 13 14 Vallox Simple Control p...

Страница 3: ...t recovery cell is bypassed when the outdoor temperature is above 14 C The heat recovery will be turned on when the outdoor temperature falls below 12 C In the AUTO position the unit will operate as f...

Страница 4: ...air is faulty Check the sensor and the wires replace as required 6 The supply air fan has stopped Check the wiring of the fan replace the fan as required 7 The extract air fan has stopped Check the wi...

Страница 5: ...on the ambient dust concentration It is recommended that the filters be replaced every spring and autumn or at the very least once a year HEAT RECOVERY CELL Check that the heat recovery cell D is cle...

Страница 6: ...grilles undo their mounting screws K 3 screws grille and remove the grilles from the fans Put the control grilles back in place after cleaning To remove the fan disconnect the quick connector H of the...

Страница 7: ...heating season begins e g during autumn maintenance check that the condensing water outlets in the bottom pool are not clogged To check this pour some water into the pool Clean as required Water must...

Страница 8: ...Enclosure protection class IP 34 Post heating Electrical resistor 1500 W Pre heating Additional heating Fans Supply air Extract air 0 119 kW 0 9 A EC 0 119 kW 0 9 A EC Specific energy consumption SEC...

Страница 9: ...71 74 78 83 85 88 88 54 57 63 66 70 75 78 79 80 LWA dB A 43 53 57 61 65 68 71 72 74 35 40 45 49 53 55 58 59 60 Sound pressure level coming through the envelope of the unit in the room in which it is i...

Страница 10: ...t link between connectors 3 and 5 from the female side of the control panel connector Post heating control PWM level adjustment 4 5 6 Protective earth to a separate block 7 8 9 1 Supply air fan 2 3 Ex...

Страница 11: ...rminal connector GND S GND S MC VENTILATION UNIT Four terminal connector MV VENTILATION UNIT GND AN I RM I RM O E I LED E O PROGRAMMING CONNECTORS OF THE MOTHERBOARD CONTACT DATA GUARD FUNCTION NORMAL...

Страница 12: ...485 Common RH optional 946147 Nomak 2x2x0 5 0 5 0 10V LED G G0 Y1 Y2 DI1 A1 Y3 A2 Y4 U1 A B C S DI2 G0 Vallox Procontrol 949034 S LED S B term CONFIG Control signal S Cooker hood or boost switch 11 2...

Страница 13: ...0 30 11 84 84 35 30 35 7 14 kpl 550 30 25 25 30 Wall mounting plate 283 166 6 604 Bottom edge of the wall mounting plate The top surface of the side panel of the unit can be installed against the nish...

Страница 14: ...ng plate Installing the ventilation unit to the ceiling mounting plate Remove the unit door Lift the unit and take the wires through the opening in the ceiling mounting plate Lift the ventilation unit...

Страница 15: ...k siphon Installation height 53 mm installation space 73 mm outer diameter of the duct 12 mm Location of the condensing water outlets R and L models If the Vallox Silent Klick siphon does not fit into...

Страница 16: ...225 6 HR cell 933260 7 Lower support for the HR cell 4102504 8 Upper support for HR cell 3467200 9 Filter frame extraction 978226 10 Coarse filter for extract air 978227 NO Part Product number 11 HR c...

Отзывы: