2.4. Antifreeze and preheating

Water condensing from extract air may freeze in the heat recovery cell (4). Freezing can be
prevented by stopping the supply air fan (standard function) or by using a preheating resistor
(see Section 2.4.4.). Both functions are automatic.

Vallox 132 E VKL

Vallox 132 E VKL model includes a water radiator antifreeze thermostat (B). When there is
a risk of freezing in the radiator, the antifreeze thermostat stops both fans and the self-actuated
dampers (5) of the fans close.

2.4.1. Stopping of supply air fan

Antifreeze thermostat (A) of the heat recovery cell stops the supply air fan whenever the
temperature of extract air goes down to circa + 5 

°

C. The fan restarts when temperature has

risen by three degrees, i.e. to +8 

°

C. The threshold value of the thermostat can be adjusted.

2.4.2. Antifreeze of post-heating radiator of Vallox 132 E VKL

The VKL model has an antifreeze thermostat (B) for the water radiator and self-actuated
dampers (5) for the fans. When there is a risk of the radiator freezing, the thermostat (B) stops
all functions of the unit and the self-actuated dampers of the fans close at the same time. This
happens when the temperature of the water radiator is lower than the value set at the
thermostat. As soon as the temperature of the radiator has risen, the unit automatically restarts
and the dampers open. The thermostat has been factory set to stop at circa +5 

°

C and to

restart at +10 

°

C.

2.4.3. Preheating

Vallox 132 E comes standard with a preheating radiator (2). 

The factory-preset setpoint of the

preheating radiator thermostat is 0 

°

C, i.e. it is not used.

 A separate thermostat (C) for preheating

measures the temperature of exhaust air. The preheating radiator switches on when exhaust
air temperature goes below the setpoint of the thermostat. If exhaust air temperature continues
to go down, the antifreeze thermostat (A) of the HR cell of Vallox 132 E stops the supply air
fan. The preheating resistor (2) switches off when exhaust air temperature is by circa 3 

°

C

higher than the value set for the thermostat.

Note!  You can adjust the antifreeze thermostats (C and A) for Vallox 132 E preheating radiator and
HR cell. However, observe the following things:

Taking preheating into use and adjusting it

 If you wish to use the preheating radiator, the recommended setting for the thermostat (C)
is circa +5 

°

C...+ 10 

°

C, but in any case a little higher than the setting for the HR cell

antifreeze thermostat (A) of Vallox 132 E. In this case the preheating resistor will become
active before the fan stops, which means that preheating is truly beneficial.

Instructions for antifreeze thermostat adjustment

•  You may check how antifreeze works by comparing the functioning of the supply air fan

and the preheating radiator. If the fan stops before the preheating radiator (2) switches
on to heat, you have to adjust the HR cell antifreeze thermostat (A) somewhat lower, from
+5 

°

C to +3 

°

C for example. Alternatively, you may increase the setting for the thermostat

(C) of the preheating radiator.

•  Observe the difference in how the thermostats function. The scales in the thermostats

indicate the temperature in which they switch on. In other words, the supply air fan of
Vallox 132 E stops at a temperature that is circa 3 … 5 

°

C cooler than the scale indicates.

• The preheating radiator heats even if the supply air fan is stopped. Consequently,

underpressure causes air coming from the outside to become warmer before the cell,
shortening the time during which the fan is stopped.

VALLOX 132 E/VKL

A

C

B

6

INSTRUCTIONS FOR USE

© VALLOX • We reserve the right to make changes without prior notification

Connection box cover plate

1

2

Vallox 132E R

Vallox 132 E VKL R

4

5

3

Thermostats (behind cover plate)

Vallox 132 E thermostats
(electric post-heating radiator)

A  Antifreeze thermostat of heat

recovery cell

B Post-heating 

thermostat

(regulation of supply air
temperature)

C Preheating 

thermostat

Vallox 132 E VKL thermostats
(water-circulating post-heating
radiator)

A  Antifreeze thermostat of heat

recovery cell

B Post-heating 

antifreeze

thermostat

C Preheating 

thermostat

Содержание 132 E Series

Страница 1: ...1 09 410E 29 1 2010 Code 3550 E VALLOX INSTRUCTIONS FOR USE AND MAINTENANCE MODELS VALLOX 132 E VALLOX 132 E VKL VALLOX We reserve the right to make changes without prior notification Vallox E 132...

Страница 2: ...hood VALLOX 1302 E has been initially adjusted for normal circumstances in your home Ventilation adjustment is needed mainly in the following circumstances VALLOX 132 E models Code 3550 E Models Vallo...

Страница 3: ...1 2 What are the characteristics of adequate ventilation Indoor air stays fresh in all the rooms of the dwelling also in bedrooms during night Without adequate ventilation carbon dioxide content tends...

Страница 4: ...m and maximum speeds and one of them is chosen in accordance with occupancy on the basis of the instructions given by automatic remote monitoring control with week clock for instance For more detailed...

Страница 5: ...at not included in the unit delivery In detached houses it is customary to use water glycol mixture as the liquid in order to prevent the freezing of the radiator Heating of air depends on the tempera...

Страница 6: ...tor 2 switches off when exhaust air temperature is by circa 3 C higher than the value set for the thermostat Note You can adjust the antifreeze thermostats C and A for Vallox 132 E preheating radiator...

Страница 7: ...hich captures fine dust pollen and dust not seen to the eye and a G3 class coarse filter A for insects and heavy pollen for instance There is a G3 coarse filter C on the extract air side The filters n...

Страница 8: ...ance When you open the door of Vallox132 E the security switch T turns voltage off You can also wash the filters with 25 30 C warm water and washing up liquid pressing them smoothly Do not handle the...

Страница 9: ...o remove the balancing pieces attached to the propellers If you use water in cleaning the unit or its parts do not let it flow into the electrical parts 3 2 1 Radiators I Post heating radiator Electri...

Страница 10: ...xternal grille contrary to what is said in the installation instructions and has been clogged or by the closing of the supply air valves in the rooms 3 4 Condensing water During the heating season hum...

Страница 11: ...ch the cell may freeze Compare with list item 1 Supply air fan stops and starts too frequently The difference between the stopping and starting temperatures is too small The preheating radiator does n...

Страница 12: ...VALLOX We reserve the right to make changes without prior notification 1 09 410 E 29 1 2010 PDF VALLOX 132 E VKL Vallox Oy Myllykyl ntie 9 11 FI 32200 Loimaa Tel 358 10 7732 200 www vallox com...

Страница 13: ......

Отзывы: