Single & Dual Zone Heat Trace Control Panel | Valin Corporation
SET UP
FIG. 4-14 ALARM DELAY SETTINGS DESCRIPTION
In the
Alarm Delay Settings Menu
, set the time interval for which an alarm will be activated after an alarm state
has been entered. This feature is to prevent nuisance alarms, such as the User Low Temperature Alarm on
system start up. If alarm state resolves before the specified time, no alarm events, such as circuit shutdown, will
occur. Units of time are in milliseconds.
1. High Current Alarm Time Delay
- Set the delay time (500-60,000miliseconds) for an alarm to be activated
after a High Current alarm state has been entered.
2. Low Current Alarm Time Delay
- Set the delay time (500-60,000miliseconds) for an alarm to be activated
after a Low Current alarm state has been entered.
3. High Temperature Alarm Time Delay
- Set the delay time (500-60,000miliseconds) for an alarm message
to be activated after a High Temperature alarm state has been entered.
4. Low Temperature Alarm Time Delay
- Set the delay time (500-60,000miliseconds) for an alarm to be
activated after a Low Temperature alarm state has been entered.
5. High GFEP Alarm Time Delay
- Set the delay time (500-10,000miliseconds) for an alarm to be activated
after a High GFEP alarm state has been entered.
6. Back
- Return to
Alarm Settings Menu
.
39