Valent VX Series Controller
45
VARIABLE
DESCRIPTION
ACTIVE
TEXT
INACTIVE
TEXT
BACNET
MODBUS
OBJECT
INSTANCE
OBJECT
TYPE
ACCESS
HYST
INDEX
REGISTER
TYPE
SIZE
Supply_Duct_Static_
Pressure_Set Point
Supply Duct Static Pressure
Set Point
38
AV
ReadCOV_
Commandable
0.1
40075
Holding
2
Space_CO2_Set Point
Space CO2 Set Point
39
AV
ReadCOV_
Commandable
0.1
40077
Holding
2
SF_Control_Signal_
BMS
BMS to control signal for
supply fan speed
133
AV
ReadCOV_
Commandable
0.1
40083
Holding
2
EF_Control_Signal_
BMS
BMS to control signal for
exhaust fan speed
134
AV
ReadCOV_
Commandable
0.1
40085
Holding
2
OAD_Control_Signal_
BMS
Allows the BMS to control
OAD position. True = BMS.
False = Local.
136
AV
ReadCOV_
Commandable
0.1
40089
Holding
2
Outside_Air_Damper_
Minimum_Set Point
Outside Air Damper
Minimum Set Point
137
AV
ReadCOV_
Commandable
1
40091
Holding
2
Aux_BMS_Analog_
Output_1
BMS Commanded auxilary
analog output
138
AV
ReadCOV_
Commandable
0.1
40093
Holding
2
Aux_BMS_Analog_
Output_2
BMS Commanded auxilary
analog output
139
AV
ReadCOV_
Commandable
0.1
40095
Holding
2
Aux_BMS_Analog_
Output_3
BMS Commanded auxilary
analog output
140
AV
ReadCOV_
Commandable
0.1
40097
Holding
2
Aux_BMS_Analog_
Output_4
BMS Commanded auxilary
analog output
141
AV
ReadCOV_
Commandable
0.1
40099
Holding
2
Cooling_Coil_Setpoint_
Max
Maximum Coil Leaving
Setpoint
313
AV
ReadCOV_
Commandable
0.1
40101
Holding
2
Appendix E: Points List