VENTING
Information on Various Venting Routes and Components Important:
It is always best to locate the
fireplace in such a way that minimizes the number of offsets and horizontal vent length. Since it is very
important that the venting system maintain its balance between the combustion air intake and the flue
gas exhaust, certain limitations as to vent configurations apply and must be strictly adhered to.
The graph showing the relationship between vertical and horizontal side wall venting will help to determine
the various vent lengths allowable. The horizontal vent run refers to the total length of vent pipe from the flue
collar of the fireplace to the face of the outer wall. Venting termination shall not be recessed into wall or siding.
WARNING
When an existing gas fireplace heater is removed or replaced,
the original venting system may no longer be sized to properly vent
the attached appliances.
4.2 Damper Adjustment
This unit has an adjustable damper for use with vertically terminated units only. The damper is shipped
in a fully open position and may be adjusted per installation. To adjust, loosen the Phillips screw and
rotate handle towards the left to close. We recommend a 1/3 closed on installations above 30 ft.
WARNING
Adjust damper for vertically terminated units only.
Do not adjust for horizontally terminated units
DAMPER