Figures 7 and 8 show wiring methods using
local and zone connector blocks, and contact
closure zone applications.

7. Test speaker wiring for short circuits.

Measure the resistance of each Home Run
wiring with an ohmmeter.  Any pair indicating
a value of less than 15 Ohms must be
rechecked for possible shorted wiring or
speakers.  Correct any problems and retest.

8. Make zone connections to Controller and

ZEU (see Figures 5 thru 7).
The zone connectors on the Controller and
ZEU can accommodate up to two 22 AWG
wires or four 24 AWG wires per zone output.
Check zone option switch setting with Zone
Map and Zone Configuration tables as you
connect each zone.

NOTE:  DO NOT over tighten zone
connector screws.

Powering Up System

With all zones wired and connected to the
Controller and ZEU(s), initial testing can begin.
Once initial testing is done, you can begin to
program the Controller with the features for each
zone.

1. Plug the power cord into the AC input

connector on the AmpliCenter®. the following
should happen:
a. The green Power LED on the

AmpliCenter will turn on and stay on.

b. The green Page Access LED on the

AmpliCenter also turns on, but will go out
after a few seconds.

c. On the Controller, verify that the green

Phone System Enabled LED is off.

d. On the Controller, verify that the yellow

Attendant Access Enabled LED is off.

e. The green Power LED on the ZEU(s) will

turn on and stay on.

NOTE:  If during power up, the system does
not respond as described, refer to the
Troubleshooting section of this guide and/or
the PagePac® Plus System Installation and
Configuration guide for detailed
troubleshooting.

2. Begin programming the Controller.
A quick reference card for telephone
programming, along with detailed programming
instructions, can be found in the PagePac Plus
System Installation and Configuration Guide,
Programming.

TROUBLESHOOTING

Some common problems encountered when the
paging system is not operating are described
below.  Check each item in the order listed.

1.  No AC power to AmpliCenter or Controller

(they supply power to the ZEU(s)).

2. Host telephone system failure.
3. Host system page port failure.
4. A hardwire disconnect between host system

and Controller.

5. AmpliCenter, Controller or ZEU zone

switches or DIP switch settings tampered
with.

If the problem has not been resolved by checking
the preceding items, refer to the troubleshooting
tables in the PagePac Plus Installation and
Configuration Guide.

Controls and Indicators, Terminals
and Connectors

Figure 9 shows the controls and indicators,
terminals and connectors on the rear panel of the
ZEU(s).  Table 1 identifies them by function.

Table 1.  Controls and Indicators, Terminals

and Connectors

1

Zone option 3-position slide switch: 70V audio
out, contact closure input and contact closure
output.

2

Zone connector for expansion zones: plus,
minus and ground screw terminals.

3

8-pin Molex connector from controller: power,
control and audio or previous ZEU.

4

8-pin Molex connector to additional ZEU:
power,  control and audio.

5

DIP switch to be set when one, two or three
ZEU(s) are used.

Содержание V-5335100

Страница 1: ...all power before installing equipment 1 Mount the Zone Expansion Unit s ZEU to either a wall cabinet or a rack below the controller 2 Connect 8 pin Molex from Controller to first ZEU and next ZEUs if used NOTE Up to 3 ZEUs can be used providing up to 56 paging and or control zones 3 Set DIP switches on each ZEU s 4 Set the Zone Option switches on the Controller and ZEU s NOTE For each zone used no...

Страница 2: ...stem does not respond as described refer to the Troubleshooting section of this guide and or the PagePac Plus System Installation and Configuration guide for detailed troubleshooting 2 Begin programming the Controller A quick reference card for telephone programming along with detailed programming instructions can be found in the PagePac Plus System Installation and Configuration Guide Programming...

Страница 3: ...ensions and Weights Height 1 75 4 45cm Width 16 00 40 64cm 19 00 48 26cm with brackets attached Depth 6 88 17 48cm Weight 3 0 lbs 1 36kg Electrical Relay Contacts Control Contact Closure Contacts are rated at 120VAC 50VDC at 1 Amp Audio Zone Contacts are rated at 2 Amps Temperature Range 0 to 40 C 32 to 104 F operational 40 to 66 C 40 to 150 F storage and shipment Humidity Range 5 to 95 non conden...

Страница 4: ...NT 12 24 TYPICAL 19 10 TEL LINE INPUT CHANNELS POWER POWER PagePac Plus AmpliCenter D300 PagePac Plus Controller Call Stacker PagePac Plus AmpliCenter D300 PagePac Plus Controller Call Stacker Figure 2 Rack Mounted Hardware Figure 3 8 pin Molex Connector from Controller to Zone Expansion Unit s ...

Страница 5: ...5 Figure 4 Setting Zone Expansion Unit Dip Switches Figure 5 Setting Zone Option Switches on Controller and Zone Expansion Units ...

Страница 6: ...6 Figure 6 Speaker Wiring Methods Figure 7 Zone Wiring Using Connector Blocks ...

Страница 7: ...7 INPUT CONTACT CLOSURE Figure 8 Speaker and Contact Closure Zone Wiring to Controller Figure 9 Zone Expansion Unit Back Panel ...

Страница 8: ... to Valcom are prepaid 5 all units out of warranty are subject to a service charge The service charge will cover minor repairs major repairs will be subject to additional charges for parts and labor This warranty is in lieu of and excludes all other warranties expressed or implied and in no event shall Valcom Inc be liable for any anticipated profits consequential damages loss of time or other los...

Отзывы: