Trouble Guide
7.1
Check “Err Lock Result”
Internally in IHP24 there is a hardware foundation fieldbus module. This module communicates
with the rest of the hardware in IHP24 via a local modbus interface. This interface needs to run at a
fixed setup.
If the “ERR_LOCK_RESULT” parameter is not “Ok” .. but “COMM Err”
On the IHP24 enter the setup menu.
In the Local Display Menu System on the IHP24 go to “Setup Menu”
2. Advanced
→
6.Modbus
→
2.Baudrate
•
Select 38400 baud
2. Advanced
→
6.Modbus
→
1.ID
•
Select 1
2. Advanced
→
6.Modbus
→
3.Parity
•
Select Even
2. Advanced
→
6.Modbus
→
4.Stopbits
•
Select 1
Remember to save when you leave the menu system.