Precipitation Intensity Reset
(aXZRI)
This command resets the rain and hail intensity parameters Ri, Rp, Hi,
and Hp.
Command format in ASCII and NMEA 0183:
aXZRI<cr><lf>
Command format in SDI-12:
aXZRI!
Example (ASCII):
0XZRI<cr><lf>
0TX,Inty reset<cr><lf>
Example (SDI-12):
0XZRI!
0<cr><lf>
(= device address)
Example (NMEA 0183)
:
0XZRI<cr><lf>
$WITXT,01,01,11,Inty reset*39<cr><lf>
where
a
=
Device address
XZRI
=
Precipitation intensity reset command
<cr><lf>
=
Command terminator in ASCII and NMEA 0183
!
=
Command terminator in SDI-12
NOTE
The precipitation counter and precipitation intensity parameters are
reset also when the supply voltage is disconnected, the command
aXZ
is issued, precipitation counter reset mode is changed, or when the
precipitation/surface hits units are changed.