background image

Technical Reference _________________________________________________________________  

14 ___________________________________________________________________ M211586EN-A 

Operation Pressure Object 

User can set current atmospheric pressure to improve the calculation 

accuracy of pressure dependent humidity parameters.  

Table 17 

Operation Pressure Object Properties 

Property 

Data type 

Writable 

Value or Initial Value 

Object Identifier 

BACnet Object Identifier 

No 

00 80 00 01 (hex) 

Object Type = 2,  

Instance = 1  

Object Name 

Character String 

No 

"OPER P" 

Object Type 

BACnet Object Type 

No 

2 (Analog Value) 

Present Value 

Real 

Yes 

1013.25 

Description 

Character String 

No 

"Operation  Pressure" 

Units 

BACnet Engineering Units 

No 

133 (hectopascals) 

Status Flags 

BACnet Status Flags 

No 

0 (FAULT == FALSE) 

Event State 

BACnet Event State 

No 

0 (NORMAL) 

Out of Service 

BOOLEAN 

No 

0 (FALSE) 

 

Present Value 

Two pressure related objects (Pressure and Altitude) are linked together. 

If Present Value in object is changed by user, Present Value in another 

object is  changed accordingly. 

Status Flags 

Table 18 

Status Flags 

Flag 

State 

Cause 

IN_ALARM 

FALSE 

Always FALSE 

FAULT 

FALSE 

Always FALSE 

OVERRIDDEN 

FALSE 

Always FALSE 

OUT_OF_SERVICE 

FALSE 

Always FALSE 

 

Event State 

Event State value is always NORMAL. 

Out of Service 

Out of Service value is not writeable.    

Содержание WINDCAP WMT52

Страница 1: ...TECHNICAL REFERENCE BACnet Protocol Information Conformance Statement for HMW90 Series M211586EN A...

Страница 2: ...hout prior written permission of the copyright holder Translated manuals and translated portions of multilingual documents are based on the original English versions In ambiguous cases the English ver...

Страница 3: ...ject_Name 7 System_Status 7 Protocol_Services 8 Database_revision 8 Relative Humidity object 8 Status Flags 9 Reliability 9 Event State 9 Out of Service 9 Temperature Object 10 Units 10 Status Flags 1...

Страница 4: ...Manual This manual describes the BACnet protocol implementation of the HMW90 series digital transmitters The same information is included as Appendix A in the HMW90 Series User s Guide Version Inform...

Страница 5: ...on Version 1 Revision 4 BACnet Standardized Device Profile Annex L BACnet Operator Workstation B OWS BACnet Building Controller B BC BACnet Advanced Application Controller B AAC BACnet Application Spe...

Страница 6: ...Annex J Foreign Device ISO 88023 Ethernet Clause 7 ANSI ATA 878 1 2 5 MB ARCNET network Clause 8 ANSI ATA 878 1 RS485 ARCNET network Clause 8 baud rates ________ Master Slave Token Passing MS TP mast...

Страница 7: ...use 6 Annex H BACnet Tunneling Router over IP BACnet IP Broadcast Management Device BBMD Does the BBMD support registrations by Foreign Devices Yes No Character Sets Supported UTF 8 ANSI X3 4 IBM Micr...

Страница 8: ...Yxxxxxxx UV Nonvolatile Object_Type BACnetObjectType ENUMERATED N R 8 Device Object Fixed System_Status BACnetDeviceStatus ENUMERATED N R 0 Operational Volatile Vendor_Name Character String N R Vaisal...

Страница 9: ...ile Max_Info_Frames Unsigned N R O 1 Fixed Segmentation_Suppo rted BACnetSegmentation ENUMERATED N R 3 No segmentation Fixed APDU_Timeout Unsigned N R 3000 ms Fixed APDU_Retries Unsigned N R 0 Fixed D...

Страница 10: ...e Conformance Code Value or Initial Value Persistence Object_Identifier BACnetObjectIdentifier No R 00 00 00 02 hex Object Type 0 Instance 2 Nonvolatile Object_Name CharacterString No R RH Nonvolatile...

Страница 11: ...Reliability not 0 OVERRIDDEN FALSE Always FALSE OUT_OF_SERVICE FALSE Present Value may NOT be written via BACnet TRUE Present Value may be written via BACnet Reliability Table 6 Reliability State Caus...

Страница 12: ...s Nonvolatile Status_Flags BACnet Status Flags BIT STRING Yes when OoS R 0 FAULT FALSE Volatile Reliability BACnet Reliability ENUMERATED Yes when OoS O 0 NO FAULT DETECTED Volatile Event State BACnet...

Страница 13: ...y Table 10 Reliability State Cause 0 NO_FAULT_DETECTED 1 NO_SENSOR No contact to measurement module 2 OVER_RANGE T over 80 C 3 UNDER_RANGE T under 40 C 7 UNRELIABLE_OTHER Other measurement error Event...

Страница 14: ...f dry air Table 13 Calculated Humidity Object Properties Property Data type Application Type Writable Conformance Code Value or Initial Value Persistence Object_Identifier BACnetObjectIdentifier No R...

Страница 15: ..._SERVICE FALSE Present Value may NOT be written via BACnet TRUE Present Value may be written via BACnet Reliability Reliability of calculated humidity objects depends on reliability of RH measurement...

Страница 16: ...ACnet Object Type No 2 Analog Value Present Value Real Yes 1013 25 Description Character String No Operation Pressure Units BACnet Engineering Units No 133 hectopascals Status Flags BACnet Status Flag...

Страница 17: ...e Present Value Real Yes 0 0 Description Character String No Operating Altitude Units BACnet Engineering Units Yes 31 33 meters feet Status Flags BACnet Status Flags No 0 FAULT FALSE Event State BACne...

Страница 18: ...tiple B DS WPM B Data Sharing COV Unsolicited A DS COVU A Data Sharing COV Unsolicited B DS COVU B Alarm and Event Notification Internal B AE N I B Alarm and Event ACK B AE ACK B Alarm and Event Infor...

Страница 19: ...firmedPrivateTransfer ConfirmedTextMessage CreateObject DeleteObject DeviceCommunicationControl Disconnect Connection To Network Establish Connection To Network GetAlarmSummary GetEnrollmentSummary Ge...

Страница 20: ...www vaisala com M211586EN...

Отзывы: