Chapter 4 _________________________________________________________________ Operation
VAISALA ________________________________________________________________________ 63
Set BACnet Parameters
Use the
BACNET
command to show or set some of the transmitter’s
BACnet parameters. You can also use the
BACNET
command to
reinitialize the BACnet stack of the transmitter without having to reset or
power cycle the transmitter.
BACNET
[
parameter_name
[
parameter_value
]] [
reinit
]<cr>
where
parameter_name = Name of the BACnet parameter to change.
Available parameters are:
Instance
: BACnet instance number. Unsigned value
in range 0 ... 4194302.
Name
:
BACnet Object_Name shown in the Device
object. String value, no spaces.
Description
:
BACnet Description shown in the
Device object. String value, no spaces.
Location
: BACnet Location shown in the Device
object. String value, no spaces.
Password
: Password used in ReinitializeDevice
service. String value, no spaces.
MAX_MASTER
:
Max_Master parameter in Device
object. Unsigned value, range 1 ... 127.
parameter_value = New value of the parameter. See descriptions above
for allowed values.
reinit
= Reinitializes the BACnet stack. Must be given as the
only argument for the
BACNET
command.
Example (show BACnet parameters):
>
bacnet
Instance : 6 (00000006h)
Name : HMW95_H2330001
Location : Location
Description : Description
Password : 1234
MAX_MASTER : 127 (007Fh)
COV_Interval : 0
Autobaud_Interval : 10