7. Technical data
7.1 HMM170 specifications
Table 7 HMM170 measurement performance
Property
Description/Value
Relative humidity
Measurement range
0 … 100 %RH
Accuracy
at +15 … +25 °C (59 … +77 °F)
±1 %RH (0 … 90 %RH)
±1.7 %RH (90 … 100 %RH)
at −20 … +40 °C (−4 … +104 °F)
± (1.0 + 0.008 × reading) %RH
at −40 … +180 °C (−40 … +356 °F)
± (1.5 + 0.015 × reading) %RH
Factory calibration uncertainty at
+20 °C (+68 °F)
±0.6 %RH (0 … 40 %RH)
±1.0 %RH (40 … 90 %RH)
±1.1 %RH (90 … 95 %RH)
Humidity sensor types
HUMICAP
â
R2C
HUMICAP
â
180L2
HUMICAP
â
180VC
T
90
50 s with steel mesh filter
60 s with sintered filter
Temperature
Measurement range
−70 … +180 °C (−94 … +356 °F)
Temperature sensor
Pt100 RTD Class F0.1 IEC 60751
Typical accuracy at +20 °C (+68 °F)
±0.2 °C (± 0.36 °F)
1)
Including non-linearity, hysteresis and repeatability.
2) With HUMICAP
â
180VC sensor, accuracy is not specified below −20 °C (−4 °F) operating
temperature.
3) Defined as ±2 standard deviation limits. Small variations possible; see also calibration
certificate.
4) At +20 °C (+68 °F) in 0.1 m/s air flow with Vaisala HUMICAP
â
R2C sensor.
HMM170 User Guide
M212259EN-D
26