Appendix
0020291544_01 Hydraulic Station Installation and maintenance instructions
49
Setting level
Values
Unit
Increment, select, ex-
planation
Factory setting
Setting
Min.
Max.
Compr. current limit
1
5
–
7 kW: 13
–
16 A
12 kW: 20
–
25 A
Fan boost
3)
52
70
1
70
Compr. noise reduct.
2)
40
60
%
1
40
Only for products with cooling:
Cooling technology
None
Active
cooling
None, active cooling
None
Intermediate heat exchanger
Yes
no
Yes, No
Software version
Current value of the
control PCB (HMU
indoor unit xxxx, HMU
outdoor unit xxxx) and
the display (AI xxxx)
xxxx.xx.xx
Installer level
→
Resets
→
Statistics
→
Reset statistics?
Yes, No
No
Maintenance messages
→
Reset
maintenance message
Yes, No
No
High-pressure switch
→
Reset
fault?
Yes, No
No
Factory settings
→
Restore fact-
ory settings
Yes, No
No
Screed drying
2)
Off, 1
–
29
Off
Installer level
→
Start inst. assistant
→
Language
Languages available for
selection
02 English
Syst. control avail.?
Yes
no
Yes, No
Im. heater power supp.
230 V
400 V
Im. heater outp. range
External
9
kW
230 V:
1
–
6: 1 kW
–
6 kW
400 V:
1
–
9: 1 kW
–
9 kW
6 or 9
Cooling technology
No cool-
ing
Active
cooling
Compr. current limit
13
25
A
1
5
–
7 kW: 13
–
16 A
12 kW: 20
–
25 A
MO relay
None, fault signal, ext.
immersion heater, DHW
3WV
None
Intermediate heat exchanger
Yes
no
Yes, No
Check program: Purge building
circuit
Yes
no
Yes, No
no
Contact details Telephone num-
ber
Phone number
0
–
9
Empty
End the installation assistant?
Yes, back
1)
See the overview of fault codes: Fault lists are only available, and can only be deleted, if faults have occurred.
2)
This parameter does not appear if a system control is connected.
3)
This parameter is only available in the products for Spain