0020200905_02 Operating and installation instructions

15

Setting level

Values

Unit

Increment, select

Default
setting

Min.

Max.

Basic settings

Enter zone name

ZONE1

1

10

A to Z, 0 to 9, space

ZONE1

Installer level

Enter code

000

999

1

000

A.3 Troubleshooting

Symptom

Possible cause

Measure

Display remains dark

Software error

1.

Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.

2.

If the fault persists, inform the competent
person.

No changes in the
display when the
rotary knob is turned

Software error

1.

Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.

2.

If the fault persists, inform the competent
person.

No changes in the
display when the se-
lection buttons are
pressed

Software error

1.

Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.

2.

If the fault persists, inform the competent
person.

Lines appear instead
of set and read-out
values

Software error

1.

Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.

2.

If the fault persists, inform the competent
person.

B For the competent person

B.1 Installation assistant

Setting

Values

Increment, select

Default setting

Min.

Max.

Language

Languages available
for selection

English

Remote control address

1

8

1

1

Содержание VR 91

Страница 1: ...en Operating and installation instructions Remote control unit VR 91 0020200905_02 22 11 2022...

Страница 2: ...g 7 2 9 Guarantee and customer service 7 3 For the competent person 7 3 1 Notes on the documentation 7 3 2 Product description 8 3 3 Set up 8 3 4 Installing the remote control unit in a living room 8...

Страница 3: ...fe way and understand the hazards in volved Children must not play with the product Cleaning and user maintenance work must not be carried out by children unless they are supervised Any other use that...

Страница 4: ...pliance with all inspection and maintenance conditions listed in the instructions Intended use also covers in stallation in accordance with the IP code Any other use that is not spe cified in these in...

Страница 5: ...0020200905_02 Operating and installation instructions 5 1 5 Regulations directives laws standards Observe the national regula tions standards directives ordinances and laws...

Страница 6: ...alfunctions Ensure that room air can circulate freely around the system control and that the system control is not covered by furniture curtains or other objects Ensure that all thermostatic radiator...

Страница 7: ...agents detergents solvents or cleaning agents that contain chlorine 2 8 Decommissioning 2 8 1 Decommissioning the product If you want to replace or remove the product you must decommission the heatin...

Страница 8: ...claration of conformity The declaration of conformity can be viewed at the manufacturer s site 3 3 Set up 3 3 1 Checking the scope of delivery Quant ity Contents 1 Remote control unit 1 Fastening mat...

Страница 9: ...mponents and the remote control unit start automatically All settings that you have applied using the installation assistant can be changed again at a later date via the level for the end user and com...

Страница 10: ...3 9 Resetting to factory setting You can use this function to reset all the set values that you configured using the remote control installation assistant You can access the Reset to default setting f...

Страница 11: ...ator 4 Unscrew the wall mounting base from the wall 3 13 Recycling and disposal Packaging Dispose of the packaging correctly This product is an electrical or electronic unit within the context of EU D...

Страница 12: ...n be found in the installation instructions for the sys tem control 3 15 Technical data 3 15 1 Remote control unit Rated voltage 9 to 24 V Rated surge voltage 330 V Pollution degree 2 Rated current 50...

Страница 13: ...for the system control Setting level Values Unit Increment select Default setting Min Max Information System status System Fault status Current value No fault Fault list Curr room air hum Current valu...

Страница 14: ...Saturday Sunday and Monday Fri day Saturday Sunday Monday Sunday Mo Fr 06 00 22 00 Sa 07 30 23 30 Su 07 30 22 00 Period 1 Start End Period 2 Start End Period 3 Start End 00 00 24 00 h min 00 10 Days a...

Страница 15: ...ch on all heat generators for approx 1 minute and then switch them on again 2 If the fault persists inform the competent person No changes in the display when the se lection buttons are pressed Softwa...

Страница 16: ...ment Set the correct address for the remote con trol unit on the system control in the Zone assignment function System fault Fault in the heating installation Assess the fault messages in the system c...

Страница 17: ...20200905_02 Operating and installation instructions 17 Symptom Possible cause Measure Lines appear instead of set and read out values Communication fault 1 Check the plug connection 2 Replace the cabl...

Страница 18: ......

Страница 19: ......

Страница 20: ...isher manufacturer Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Tel 49 2191 18 0 Fax 49 2191 18 2810 info vaillant de www vaillant de These instructions or parts thereof are protected by copyrigh...

Отзывы: