0020200905_02 Operating and installation instructions
15
Setting level
Values
Unit
Increment, select
Default
setting
Min.
Max.
Basic settings
→
Enter zone name
→
ZONE1
1
10
A to Z, 0 to 9, space
ZONE1
Installer level
→
Enter code
000
999
1
000
A.3 Troubleshooting
Symptom
Possible cause
Measure
Display remains dark
Software error
1.
Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.
2.
If the fault persists, inform the competent
person.
No changes in the
display when the
rotary knob is turned
Software error
1.
Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.
2.
If the fault persists, inform the competent
person.
No changes in the
display when the se-
lection buttons are
pressed
Software error
1.
Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.
2.
If the fault persists, inform the competent
person.
Lines appear instead
of set and read-out
values
Software error
1.
Switch off the mains switch on all heat
generators for approx. 1 minute and then
switch them on again.
2.
If the fault persists, inform the competent
person.
B For the competent person
B.1 Installation assistant
Setting
Values
Increment, select
Default setting
Min.
Max.
Language
Languages available
for selection
English
Remote control address
1
8
1
1