background image

VA 6-060 MXNHO
VA 6-085 MXNHO
VA 6-105 MXNHO

VA 6-020 MXNHI
VA 6-025 MXNHI
VA 6-035 MXNHI
VA 10-020 MXNHI
VA 10-025 MXNHI
VA 10-035 MXNHI
VA 6-035 MXNHKI
VA 6-050 MXNHKI
VA 6-035 MXNHDI
VA 6-050 MXNHDI

climaVAIR

DE, EN, ES, HR, IT, NL, TR, PL

Содержание VA 10-020 MXNHI

Страница 1: ...6 085 MXNHO VA 6 105 MXNHO VA 6 020 MXNHI VA 6 025 MXNHI VA 6 035 MXNHI VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6 035 MXNHKI VA 6 050 MXNHKI VA 6 035 MXNHDI VA 6 050 MXNHDI climaVAIR DE EN...

Страница 2: ...nditioner climaVAIR Multi Split Type EN VA 6 060 MXNHO VA 6 085 MXNHO VA 6 105 MXNHO VA 6 020 MXNHI VA 6 025 MXNHI VA 6 035 MXNHI VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6 035 MXNHKI VA 6 0...

Страница 3: ...nded Installation Process 17 10 4 Installation of the Condensed Water Pipe 17 10 4 1 Handling the Condensed Water Pipe 17 10 4 2 Laying of the Condensed Water Pipe 17 10 5 Installation of the Coolant...

Страница 4: ...any service of maintenance operations involving the handling of the refrigerant fluid must have the necessary certification to comply with all local and international regulations 2 Extreme Operating...

Страница 5: ...onnections and channels 5 Condensed water drainage pipe 5 1 Wall mounted type Indoor Unit The indoor unit provides acclimatised air inside the room to be acclimatised The dimensions and weights of the...

Страница 6: ...Indoor Unit plant Fig 5 4 Dimensions of the Indoor Unit lateral MODEL H I D VA 6 035 MXNHKI 260 60 100mm VA 6 050 MXNHKI 260 60 100mm Table 5 3 Dimensions of the Indoor Unit lateral 5 3 Duct type Ind...

Страница 7: ...and Table 5 5 depending on the model please consult the model nameplate The dimensions are given in mm Fig 5 6 Dimensions of the outdoor unit Legend H Height L Length D Depth A Length of valves B Dis...

Страница 8: ...Bracket 1 3 Batteries 2 4 Mounting plate 1 5 Piping support plate 1 6 Cushion 4 7 Drainage elbow 1 8 Cover 1 9 Drain tube 1 10 Steel nail cement 6 11 Screw caps 2 12 Wireclamp 1 13 Installation Manua...

Страница 9: ...20x1090x500 Net Weight kg 7 6 17 19 14 25 Panel Net Weight kg 2 8 2 8 Air Drop static pressure Pa 20 20 Pipe Connections Pipe Connection liq gas inches 1 4 3 8 1 4 3 8 1 4 1 2 includes connector for O...

Страница 10: ...not dispose of it without the proper controls 8 Installation 8 1 Qualification of the Installation Personnel Ensure that this unit is installed by authorised personnel The personnel authorised by Vai...

Страница 11: ...um 2 m E Side separation opposite side connections minimum 10 cm F Rear separation minimum 10 cm G Side separation connections side minimum 15 cm H Front separation minimum 60 cm 8 4 General Installat...

Страница 12: ...ning the condensed water E Side separation opposite side connections minimum 10 cm F Rear separation minimum 10 cm G Side separation connections side minimum 15 cm H Front separation minimum 60 cm Fig...

Страница 13: ...downs or malfunction Ensure that the assembly plate has been correctly levelled Otherwise disassemble the plate and assemble it again correctly 9 3 Installation of the Pipes 9 3 1 Methods for the Corr...

Страница 14: ...cted downwards in order to prevent shavings from getting into the pipes Mount the joining tubes carefully ensuring they cannot become displaced Ensure that they will not cause traction in the joins Eq...

Страница 15: ...the event of laying the rear piping a suitable hole must be made see Figure 9 7 Drill a hole in accordance with the diameter indicated in Figure 9 7 slightly descending to the outside Fig 9 7 Dimensi...

Страница 16: ...y possible cuts with masking tape or insulate any bare coolant piping with the corresponding insulation material used for cooling Fig 9 10 Laying the Pipes Legend 1 Heat resistant material 2 Drain pip...

Страница 17: ...ng the indoor unit in the ceiling and to make the connections immediately after mounting the indoor unit This will provide you with more space 10 2 Selecting the Assembly Location Danger of personal i...

Страница 18: ...erged in water Avoid installing the condensed water pipe with crimping Install the condensed water pipe in such a way that the distance of its free end from the floor is at least 5 cm Install the cond...

Страница 19: ...ng into the pipes Mount the joining tubes carefully ensuring they cannot become displaced Ensure that they will not cause traction in the joins Equip the coolant pipes inflow and outflow separately an...

Страница 20: ...sembly in the Ceiling Note The indoor unit is fixed to the ceiling using hooks and hanging bars threaded varilla M10 with its corresponding nuts locknuts and washers Draw the position of the fixing el...

Страница 21: ...unit see figure 10 3 Carry out the electrical connection see section 13 Note The connections in the flaring should be accessible in order to carry out the water tightness tests 10 9 Installation of t...

Страница 22: ...ossible transmission of vibration and noise installing if necessary anti vibration and soundproofing elements 11 3 Installation of the indoor unit Introduce and twist a nut on each of the rods Raise t...

Страница 23: ...sunlight Ensure that the ground has sufficient rigidity to avoid vibrations Check that there is sufficient space to observe the minimum distances see Figure 121 Check that neighbours are not disturbed...

Страница 24: ...tion Danger of wear in the coolant pipes Bend the pipe carefully to prevent choking or breaks Cut the pipes leaving enough extra piping hanging over to enable the unit to be hooked up at the outdoor u...

Страница 25: ...able Warning Danger of breakdowns or malfunction Size the electric wiring with sufficient capacity Warning Danger of breakdowns or malfunction Compliance with the Standard EN 61000 3 11 Check that the...

Страница 26: ...ight of the body by unscrewing it see Figure 13 1 Fig 13 1 Wiring Cover Insert the cable from the outside Using the same hole through which the coolant pipes are installed or are going to be installed...

Страница 27: ...d Otherwise the machine will not work Warning Installation should be done with a proper earth connection and each unit should be properly earthed Otherwise the machine will not work Secure the cable i...

Страница 28: ...8 0 8 Inteconnect Shield or not YES NO YES YES YES Immediatte residual current protector A 0 03 0 03 0 03 0 03 0 03 0 03 Electric Wiring 13 Supply VA 10 020 MXNHI VA 10 025 MXNHI VA 10 035 MXNHI VA 6...

Страница 29: ...ch on the indoor unit with the remote control by pressing the ON button When the unit switches on it automatically goes into direction setup mode To set the direction of the indoor unit just press the...

Страница 30: ...B Note In the case of Cassette indoors first take out the panel and filters take off the flaps and the front cover disconnect the swing motor connectors from the PCB and take out the lower part of the...

Страница 31: ...d you will hear 4 beeps Release the emergency button Switch on the indoor unit with the remote control by pressing the ON button The LCD display board will display number 1 When the unit switches on i...

Страница 32: ...must be periodically checked for leakage Take the necessary actions to ensure these tests are performed and the results correctly logged into the maintenance record of the machine The leakage test mus...

Страница 33: ...5 4 If there are no leaks continue Remove the combined meter with the joining hoses and faucets Open the two and three way valves by twisting the rod anticlockwise as far as it will go Fig 15 6 Openin...

Страница 34: ...dis connected or wrong address setting of indoor units or faulty power supply or faulty PCB Abnormal communication between wired controller and indoor unit PCB 7 Times Wrong connection or use the wir...

Страница 35: ...on troller be disconnected faulty PCB Drainage System abnormal 08 Pump motor disconnected or at wrong position or the float switch broken down or the float switch disconnected or at wrong position Ind...

Страница 36: ...or bad air circulation of outdoor unit DC fan motor fault 24 Fan is blocked or the terminal is disconnected from the PCB Faulty 4 way valve switching on 25 Coil of 4 way valve is disconnected or fault...

Страница 37: ...ted or broken or at wrong position or short circuit Faulty EEPROM on indoor unit PCB 5 Faulty indoor unit PCB Abnormal communication between indo or and outdoor unit 6 Wrong connection or the wires be...

Страница 38: ...fan motors when heating or refrigerant over abundance 10 System low pressure pro tection Low pressure switch is disconnected or low pres sure switch worked or Te too low and faulty outdo or fan motor...

Страница 39: ...or faulty SPDU or ISPM 26 Compressor be locked Faulty compressor or SPDU or ISPM 27 Compressor vibration too big Faulty compressor 28 Compressor lose position Faulty SPDU or ISPM 29 Faulty compressor...

Страница 40: ...Notes Multi Split Type Installation Manual 39...

Страница 41: ......

Отзывы: