GAS SUPPLY ADJUSTMENTS
(COMMISSIONING PART II)
1
Simultaneously press the „
i
” and
„
+
” buttons keys.
2
Keep the „
+
” button pressed until
„
d.0
” is displayed.
(The display runs from „
d.0
” to
„
d.99
” before restarting again at
„
d.0
”.)
3
Press the „
i
” button and a value
between 1 and 15 will be
displayed.
~ 5 s
5
After setting, press and hold the
„
i
” button for five seconds - or until
the display stops flashing. The new
setting value is now memorised.
The new main burner pressure can
now be checked.
If the new output is not correct
repeat steps 3 to 5.
6
To return to normal mode, press
the „
i
” and „
+
” buttons
simultaneously.
The adjustment mode is also
cancelled if no button is pushed for
a period of four minutes.
4
Use the „
+
” or „
-
” buttons to
increase or decrease the value.
Observe the U-gauge as the button
is pushed and stop pushing when
the required main burner pressure
has been achieved.
Euro B/S 065/0
Euro B/S 066/0
Euro B/S 067/0
Euro B/S 068/0
Euro B/S 069/0
Euro B/S 065/0