0020244998_04 ecoTEC plus Installation and maintenance instructions
53
Code Parameter
Values or explanations
Factory
setting
Own setting
D.026 Auxiliary relay
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not active)
10 = Solar valve (not active)
2 = External
pump
D.027 Accessory relay 1
Switching of relay 1 on the VR 40 "2 in 7" multi-func-
tional module
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not active)
10 = Solar valve (not active)
2 = External
pump
D.028 Accessory relay 2
Switching of relay 2 on the VR 40 "2 in 7" multi-func-
tional module
1 = Circulation pump
2 = External pump
3 = Cylinder charging pump
4 = Extraction hood
5 = External solenoid valve
6 = External fault message
7 = Solar pump (not active)
8 = eBUS remote control (not active)
9 = Anti-legionella pump (not active)
10 = Solar valve (not active)
2 = External
pump
D.029 Water circulation vol. actual value
Actual value in m
³
/h
Not ad-
justable
D.033 Fan speed target value
In rpm
Not ad-
justable
D.034 Fan speed actual value
In rpm
Not ad-
justable
D.035 3-way valve position
Heating mode
Parallel operation (mid-position)
DHW mode
Not ad-
justable
D.036 DHW flow rate
In l/min
Not ad-
justable
D.039 Solar inlet temp. actual value
Actual value in °C
Not ad-
justable
D.040 Flow temperature actual value
Actual value in °C
Not ad-
justable
D.041 Return temperature actual value
Actual value in °C
Not ad-
justable
D.044 Ionisation value actual value
Display field 0 to 1020
> 800 no flame
< 400 good flame
Not ad-
justable
D.046 Pump mode
0 = Relay with disable facility
1 = PWM with disable facility
0 = Relay
with disable
facility
D.047 Current outside temperature
(with Vaillant weather-compensated control)
Actual value in °C
Not ad-
justable