Operating instructions ecoTEC plus 937

12

The set value is shown in the display (

2

) during the 

setting process. After approx. 3 seconds the display 
returns to standard mode (the current heating flow 
temperature).
Normally you can adjust the knob (

1

) continuously up to 

a flow temperature of 75 °C.
However, if higher temperatures are required this can be 
achieved by adjusting the boiler parameter d.71 
(a qualified installer should make this change) up to a 
maximum of 85 °C.

4.5.2  Switching heating mode off (summer mode)

bar

i

F

P

1

Fig. 4.12   Switching off heating (summer operation)

You can switch off the heating in summer without 
switching off the hot water supply.
•  Turn the rotary knob (

1

) for setting the heating flow 

temperature all the way to the left.

4.5.3  Setting a room thermostat or weather 

compensator

i

F

P

2

1

Fig.4.13  

Setting a room thermostat or weather compensator

•  Adjust the room thermostat (

1

) and/or the radiator 

thermostatic valves (

2

) in accordance with the 

operating instructions for these accessories.

h

 Note

Vaillant supplies thermostats and time 
controllers which provide exact and economic 
room temperature regulation for improved 
operating convenience.

The boiler thus operates automatically according to the 
set parameters for the heating system (the ecoTEC 
combination boiler also provides hot water if required).
After operation is stopped the pump runs on for a short 
period to allow the heat to be completely dissipated 
from the unit. 

h

 Note

The boiler is fitted with a control unit which 
prevents unnecessary and energy-wasting 
short-term switching on and off. For this reason 
there may be a slight delay when setting a 
higher temperature on the thermostat before 
the boiler switches on.

4.6 

Status displays (for maintenance and 
servicing by the engineer)

bar

i

F

P

2

1

Fig. 4.14    Status displays

The status display provides information on the operating 
status of the appliance.
•  Press the "

i

" button (

1

) to activate the status displays.

The display (

2

) then shows the individual status codes, 

e.g. "

S. 4

“ for burner operation. The table below 

explains the most important status codes.
In switching phases, for example on starting up again 
after the flame was extinguished, the status message 
"

S.

" briefly appears.

•   Press the "

i

" button (

1

) again to switch the display 

back to normal mode.

4 Operation

Содержание ecoTEC plus 937

Страница 1: ...For the owner Operating manual ecoTEC plus 937 VUI GB Gas condensing storage combination boiler...

Страница 2: ...used by water pressure too low 13 4 7 2 Faults in ignition 13 4 7 3 Faults in the air flue gas routing 13 4 8 De commissioning 14 4 9 Frost protection 14 4 10 Maintenance and customer service 14 Appli...

Страница 3: ...ever they are required If you move out or sell the appliance pass on the documents to the buyer 1 2 Symbols used Please observe the following when operating the unit Safety instructions in this operat...

Страница 4: ...g and explosion due to a malfunction Never put the safety devices out of operation or tamper with them so as to impair their function 2 4 Modifications to the boiler and its environment No changes mus...

Страница 5: ...ctions on operation 3 1 Factory guarantee 3 1 1 Two years guarantee for ecoTEC plus units Vaillant is committed to rectify any manufacturing faults which arise during the first 24 months after install...

Страница 6: ...ons 4 Operation 4 1 Overview of the operating elements bar i F P 1 10 9 8 7 6 2 3 4 5 Fig 4 1 Operating elements ecoTEC The operating elements have the following functions 1 Display indicating the cur...

Страница 7: ...rature is set via the vrnetDIALOG accessory which means the appliance uses temperatures other than those set using the rotary knobs 9 and 10 This operating mode can only be ended via vrnetDIALOG or by...

Страница 8: ...filling pressure between 1 0 and 2 0 bar If the indicator is in the light grey area below 0 8 bar fill the system up with water before putting it into operation hNote The ecoTEC appliances come with a...

Страница 9: ...used if the heating system has water in it see Section 4 2 2 4 4 1 Setting the hot water temperature bar i F P 2 1 Fig 4 6 Setting the water temperature Switch on the appliance as described in sectio...

Страница 10: ...ture The heated water is then immediately available when you draw it off The symbol is displayed The warmstart function is de activated by turning the knob 1 in an anti clockwise direction to the end...

Страница 11: ...way to the right hand end stop The symbol is displayed Turn the knob for setting the hot water temperature to the temperature you require De activating the storage tank charging De activate the stora...

Страница 12: ...s and time controllers which provide exact and economic room temperature regulation for improved operating convenience The boiler thus operates automatically according to the set parameters for the he...

Страница 13: ...3 All the external controller set to the ON position see Section 4 5 3 a Caution Inappropriate alterations can cause damage If your boiler still does not operate properly after checking the above poin...

Страница 14: ...s not disconnected from the mains power supply Frost protection function The gas wall mounted boiler is equipped with a frost protection function If the heating feed temperature falls below 5 C with t...

Страница 15: ...20 C 20 C C 5 5 C bar bar VRT VRC i F P...

Страница 16: ...0020031573_00 GB 022007...

Отзывы: