39
ecoTEC exclusive installation and maintenance instructions / 0020017768_02
Display
Meaning
Display value/adjustable value
d.14
Pump speed target value
target value internal pump in % - possible settings:
0=Auto, 1=53, 2=60, 3=70, 4=85, 5=100 % (Factory setting: Auto)
d.17
Heating flow/return regulation changeover
0 = flow, 1 = return (factory setting: 0)
d.18
Pump mode (return flow)
0 = overrun 1 = continuous, 2 = winter (Factory setting: 0)
d.26
Changeover option relay to electronic
1 = circulation pump
2 = external pump
3 = storage charging pump
4 = vapour extraction hood
5 = external throttle
6 = external fault signal (without maintenance display)
d.27
Changeover relay 1 on the accessories module
1 = circulation pump (factory setting)
2 = ext. pump
3 = storage charging pump
4 = flue gas flap/extractor hood
5 = external gas valve
6 = external error message
d.28
Changeover relay 2 on the accessories module
1 = circulation pump
2 = ext. pump (factory setting)
3 = storage charging pump
4 = Flue gas flap/extractor hood
5 = External gas valve
6 = External error message
d.50
Offset for minimum fan speed
in rpm/10, adjustment range: 0 to 300
d.51
Offset for maximum fan speed
in rpm/10, adjustment range: -99 to 0
d.58
Activation solar post-heating
setting range: 0 to 3
0 = solar post-heating deactivated (factory setting)
3 = activation drinking water target value min = 60 °C for
solar post-heating
d.60
Number of temperature limiting shutdowns
amount
d.61
Number of fuel automatic system faults
number of successful ignitions in the last attempt
d.64
Average ignition time
in seconds
d.65
maximum ignition time
in seconds
d.68
Unsuccessful ignitions at the first attempt
number
d.69
Unsuccessful ignitions at the second attempt
number
d.70
Setting the priority changeover valve position
0 = normal mode (factory setting)
1 = centre position
2 = permanent heating position
d.71
Target value max. heating flow temperature
Adjustment range in °C 40 to 85 (Factory setting: 75)
d.72
Pump overrun time after heat retention function
Adjustment range in sec: 0, 10, 20 to 600 (Factory setting: 80)
d.73
Offset for hot start target value
Setting range: -15 K to +5 K (Factory setting: depending upon variant)
d.80
Operating hours heating
in h
1)
d.81
Operating hours hot water function
in h
1)
d.82
Hystereses in heating mode
number/100
1)
(3 equals 300)
d.83
Hystereses in hot water function
number/100
1)
(3 equals 300)
d.84
Maintenance indicator: Number of hours until the
next maintenance
setting range: 0 to 3000h and „-“ for deactivated
factory setting: „-“ (300 corresponds to 3000h)
d.93
DSN appliance variant setting
setting range: 0 to 99
d.96
Default setting
1 = Resetting adjustable parameters to factory setting
Table 9.3 Diagnosis codes in the 2nd diagnosis level
1)
In the diagnosis codes 80 to 83 5 digit figure values are stored. When selecting e.g. d.80 only the first two digits of the figure value are displayed (e.
g.10). By pressing the „i“ key, the display switches over to the last three figures (e.g. 947). The operating hours counter of the heating in this case
would be 10947 h. Pressing the „i“ again causes the display to switch back to the diagnosis point that was called up.
Troubleshooting 9