Installation 5
0020217119_01 aroCOLLECT Installation and maintenance instructions
9
Sound propagation form: An eighth of a sphere
Sound propagation for the adjacent building: On two sides
and at a right-angle.
L
WA
= L
PFA
–
10 lg S
L
WA
= Sound pressure level (dB(A))
L
PFA
= Sound power level (dB(A))
S = Sound propagation form* (clearance from the product in
m)
²
Sound propagation form: Hemisphere = 6.28
Sound propagation form: Quarter-sphere = 3.14
Sound propagation form: Eighth of a sphere = 1.57
Example
L
PFA
= 54 dB(A), max. sound power level without noise re-
duction
Sound propagation form = Hemisphere = 6.28
Distance to the product = 10 m
L
WA
= 54 dB(A)
–
10 lg (6.28 * 100)
L
WA
= 54 dB(A)
–
10 lg (628)
L
WA
= 54 dB(A)
–
28
L
WA
= 26 dB(A)
▶
Choose the installation site so that the legally required
emissions values for noise outside of buildings can be
complied with, without having to use the heat pump sys-
tem's noise reduction function, if possible.
▶
In certain weather conditions, take into consideration
the possibility of black ice forming directly in front of the
product's outlet side; if condensate escapes, the black
ice may form all around the product.
5.4
Dimensions
1192
78
5
12
56
116
2
5.5
Minimum clearances
≥ 0,3 m
≥ 0,5 m
≥ 0,5 m
≥ 3 m
ca. 0,5 m
≥ 0,5 m
< +5 °C
Clearances that must be complied with for an air/brine col-
lector