Installation and start-up
6
Installation manual neutralisation device without feed pump 0020134552_00
3
3
Installation and start-up
3.1 Checking
the
delivery
5x
1
5
4
3
8
10
9
6
7
11
2
3.1
Overview of the neutralisation device
without feed pump
Pos. Number Description
1
1
Neutralisation box
2
1
Connection for drain hose
3
1
Neutralisation medium 30 kg
(contained in delivery of the neutralisation box)
4
5
Hose clamps
5
1
Connection adaptor on the condensate drain
DN 40 of the gas-fired high-efficiency boiler
6
1
Angle piece 20 x 20 for infeed connection
7
1
T piece 20 x 20 x 20 for connecting the chimney
water drainage
8
1
Drain hose DN 19
9
1
Infeed hose DN 19
10
1
Opener
11
1
Connection for infeed hose
3.1
Scope of delivery for the neutralisation device
without feed pump
>
Check that the scope of delivery is complete (
¬
tab. 3.1
).
3.2 Function
The neutralisation device provides neutralisation of the
condensed water from gas-fired high-efficiency boilers and/
or flue gas systems made of stainless steel, plastic and
ceramic.
The condensed water from the gas-fired high-efficiency
boiler is fed into a vessel (neutralisation box). The vessel
contains the neutralisation medium which raises the pH
value of the condensed water to a neutral level. The neu-
tralisation agent can be replaced via a removable cover.
The neutralised condensed water can be fed into the drain-
age system.
3.3
Fitting the neutralisation device
a
Danger!
Risk of death from electric shock!
There is a risk of electric shock when open-
ing the gas-fired high-efficiency boiler.
>
Before opening the cover, switch off the
gas-fired high-efficiency boiler (mains
switch and fuse).
3.2
Fitting the neutralisation device without feed pump
The position numbers in the following text refer to
fig. 3.1
.
Fitting the infeed hose
>
Unscrew the yellow protective cap from the connection
(
11
).
>
Use the existing seal to fit the infeed hose.
>
Shorten the infeed hose (
9
) to the desired length.
>
Connect the infeed hose (
9
) with the connection adap-
tor (
5
) and the angle piece (
6
).
>
Secure the connection adaptor (
5
) and angle piece (
6
)
with 2 hose clamps (
4
).
>
Secure the mounted infeed hose on the connection (
11
).