11 Decommissioning

26

Installation instructions VRT 350 0020131957_01

11 Decommissioning

11.1

Replacing the controller

1.

If you want to replace the controller, disconnect all of the
connected modules from the power supply. Observe the
relevant instructions.

2.

If you want to replace the controller, first shut down the
heating installation.

3.

To do this, follow the instructions for shutting down in
the boiler instructions.

4.

Disconnect the power supply to the boiler.

5.

Disconnect the boiler from the power mains by pulling
out the mains plug or de-energising the boiler using a
partition with a contact opening of at least 3 mm.

6.

Secure the power supply to the boiler against being
switched on again.

7.

Check that there is no voltage in the boiler.

11.1.1 Removing from the wall

1.

Insert the screwdriver into the slot on the wall-mounting
base .

2.

Carefully lever the controller off the wall mounting base .

3.

Unfasten the eBUS line from the pin header on the con-
troller and from the terminal block on the boiler.

4.

Unscrew the wall-mounting base from the wall.

11.2

Recycling and disposal

The controller and the associated transport packaging con-
sist largely of recyclable materials.

Unit

If your Vaillant unit is identified with this symbol, it does

not belong with your household waste at the end of its useful
life.

In this case, make sure that the Vaillant unit and any ac-
cessories are properly disposed of at the end of their use-
ful life.

As this Vaillant unit is covered by the law regarding the mar-
keting, return and environmentally friendly disposal of elec-
trical and electronic equipment (ElektroG in Germany), the
unit can be disposed of free of charge at a municipal collec-
tion point.

Packaging

The approved qualified servicing company that installed the
unit will dispose of the transport packaging.

12 Customer service

To ensure regular servicing, it is strongly recommended that
arrangements are made for a Maintenance Agreement.

Содержание 0020124475

Страница 1: ...For the competent person Installation instructions VRT 350 VRT 350 GB IE Installation instructions ...

Страница 2: ...er Vaillant GmbH Berghauser Str 40 D 42859 Remscheid Telefon 49 21 91 18 0 Telefax 49 21 91 18 28 10 info vaillant de www vaillant de Vaillant GmbH 2012 These instructions or extracts thereof may only be printed with the written consent of Vaillant GmbH All designations of products in these instructions are brand names trade marks of the companies in question We reserve the right to make technical...

Страница 3: ... 10 5 2 Connect the controller to the boiler with a 24V RT terminal 11 6 Electrical installation 12 6 1 Connect the controller to the boiler with a 3 4 5 Terminal 12 6 2 Connect the controller to the boiler with a 24V RT terminal 13 7 Start up 14 7 1 Overview of installation assistant set up options 15 8 Operating 16 8 1 Installer level overview 17 9 Operating and display functions 20 9 1 Service ...

Страница 4: ...ts of the system These installation instructions are enclosed with the various system parts and supplementary components Furthermore observe all operating instructions enclosed with components of the system 1 3 Document storage Document handover Pass these instructions and all other applicable docu ments and if necessary any required tools to the system operator Availability of documents The syste...

Страница 5: ...d through these installation instructions carefully Carry out the activities that are described in these install ation instructions During the installation observe the following safety in structions and regulations 2 2 2 Risk of death from live connections When working in the electronics box of the boiler there is a risk of death from electric shock Continuous voltage is present on the mains conne...

Страница 6: ...ompatibility directive Council Directive 2004 108 EC Low voltage directive Council Directive 2006 95 EC 2 4 Intended use State of the art The controller is a state of the art unit manufactured in ac cordance with recognised safety regulations Even so in the event of inappropriate or non intended use damage to the appliance and other property may arise The controller controls a heating installation...

Страница 7: ...ctions 7 observance of accompanying operating installation and servicing instructions for the Vaillant product as well as for other parts and components of the system compliance with all inspection and maintenance condi tions listed in the instructions ...

Страница 8: ...ic ation plate Meaning Serial number For identification VRT XXX Unit designation V Operating voltage mA Current consumption CE label Unit complies with European standards and directives Waste container Proper disposal of the unit 3 2 Scope of delivery Quant ity Component 1 Controller 1 Fastening material 2 bolts and 2 wall plugs 1 Operating instructions Quant ity Component 1 Installation instructi...

Страница 9: ...d 6 Use the screws supplied to secure the wall mounting base 7 Connect the eBUS line to the terminal block Page 10 8 Carefully insert the controller in the wall mounting base Ensure that the pin header 5 on the wall mounting base fits into the controller connector provided 9 Carefully press the controller into the wall mounting base until the locking tabs on the controller are heard to latch into ...

Страница 10: ... using a partition with a contact opening of at least 3 mm 3 Secure the power supply to the boiler against being switched on again 4 Check that there is no voltage in the boiler 1 2 1 Controller terminal block 2 Boiler terminal block 5 Check whether the bridge is installed between termin als 3 and 4 on the PCB of the electronics box and if re quired install the bridge between terminals 3 and 4 6 C...

Страница 11: ...ower mains by pulling out the mains plug or de energising the boiler using a partition with a contact opening of at least 3 mm 3 Secure the power supply to the boiler against being switched on again 4 Check that there is no voltage in the boiler Burner off 1 2 1 Controller terminal block 2 Boiler terminal block 5 Check whether the bridge is installed between the 24 V RT terminals on the PCB of the...

Страница 12: ...ith a 3 4 5 Terminal 1 Disconnect the power supply to the boiler 2 Disconnect the boiler from the power mains by pulling out the mains plug or de energising the boiler using a partition with a contact opening of at least 3 mm 3 Secure the power supply to the boiler against being switched on again 4 Check that there is no voltage in the boiler 1 2 1 Controller terminal block 2 Boiler terminal block...

Страница 13: ...ower mains by pulling out the mains plug or de energising the boiler using a partition with a contact opening of at least 3 mm 3 Secure the power supply to the boiler against being switched on again 4 Check that there is no voltage in the boiler Burner off 1 2 1 Controller terminal block 2 Boiler terminal block 5 Check whether the bridge is installed between the 24 V RT terminals on the PCB of the...

Страница 14: ... ure for the hot water generation and heating cir cuit you must set the maximum value for the tem peratures on the boiler To do this turn the boiler s rotary knobs as far as they go in a clockwise direc tion You can use the installation assistant to make the main set tings for the heating installation The operating concept an operation example and the menu structure are all contained in the operat...

Страница 15: ...Setting Min Max Language Languages for selection English Zone 2 None 1 2 0 Control strategy 3 Two point analogue Two point Route adjustment 1 5 5 1 0 Cylinder 3 Active Inactive Active 1 Appears only if the value Analogue is set for the control strategy 2 Appears only if a VR 66 is connected 3 Appears only in the display of the main controller with Zone 1 selected ...

Страница 16: ...e controller has two operating levels the access level for the operator and the access levels for the competent person The setting and read out options for the operator the oper ating concept and an operating example are described in the operating instructions for the controller ...

Страница 17: ...ller level Service information Enter contact details Installer 1 11 Figures A to Z 0 to 9 Space Phone 1 12 Numbers 0 to 9 Space Hyphen Installer level Service information Service date Next service on Date If there is no fault the status is OK If there is a fault Fault appears here and you can read the fault message in the Fault messages section 1 Appears only if the value Analogue is set for the c...

Страница 18: ... VF1 Current value HEATING 1 Auto day temp until Current value hr min Day temperature 5 30 0 5 20 Set back temperature 5 30 0 5 15 Flow temp target Current value Flow temp current Current value If there is no fault the status is OK If there is a fault Fault appears here and you can read the fault message in the Fault messages section 1 Appears only if the value Analogue is set for the control type...

Страница 19: ...nder temperature Current value System Control type Current value 2 point analogue 2 point Distance Adjustment 1 5 5 1 0 Installer level Change code New code 000 999 1 000 If there is no fault the status is OK If there is a fault Fault appears here and you can read the fault message in the Fault messages section 1 Appears only if the value Analogue is set for the control type If the VR 66 is connec...

Страница 20: ...or can view these contact details in the display of the controller 9 1 2 Entering the service date Menu Installer level Service information Service date In the controller you can save a date day month year for the next regular service When the date for the next service date is reached the mes sage Service heater 1 is displayed in the basic display of the controller If a service date is saved in th...

Страница 21: ...mperature control Two point corresponds to an On Off control system Analogue corresponds to a modulating control system 9 2 6 Setting the distance adjustment Menu Installer level System configuration System Distance adjustment This function allows you to optimally adjust the switching behaviour of the controller to the room size or the radiator layout Positive values slower controller switching be...

Страница 22: ...ature for the heating circuit The set back temperature is the temperature to which the heating is to be reduced at times of low heat demand e g overnight 9 4 4 Reading the target flow temperature Menu Installer level System configuration HEATING 1 Flow temp target You use this function to read the target flow temperature for the heating circuit 9 4 5 Reading the current flow temperature Menu Insta...

Страница 23: ...in such a way that the heat demand of the operator is covered The temperature for the domestic hot water cylinder must be set to the maximum value in the boiler 9 5 3 Reading the current temperature of the domestic hot water cylinder Menu Installer level System configuration Domestic hot water Cyl temp current You can use this function to read the measured cylinder temperature 9 6 Changing the cod...

Страница 24: ...his case the right hand selector button has the function Display Press the right hand selector button to display a list of fault messages Note Not all error messages in the list appear automatically on the display Display Meaning Connected units Cause Fault Heater 1 Fault in Heater 1 Heat generator 1 See heater instructions Heater 1 connection is missing Connection fault Heater 1 Heat generator 1 ...

Страница 25: ...Rectifying faults 10 0020131957_01 VRT 350 Installation instructions 25 Fault Cause Remedy No changes in the display via the selector buttons Unit fault The power is switched off on at the heater ...

Страница 26: ...troller off the wall mounting base 3 Unfasten the eBUS line from the pin header on the con troller and from the terminal block on the boiler 4 Unscrew the wall mounting base from the wall 11 2 Recycling and disposal The controller and the associated transport packaging con sist largely of recyclable materials Unit If your Vaillant unit is identified with this symbol it does not belong with your ho...

Страница 27: ...Customer service 12 0020131957_01 VRT 350 Installation instructions 27 Please contact Vaillant Service Solutions for further details 0330 100 3461 ...

Страница 28: ...lant Ltd Nottingham Road Belper Derbyshire DE56 1JT Telephone 0330 100 3461 Vaillant Service Solutions 0330 100 3461 Spares Technical Enquiries 017 73 59 66 15 info vaillant co uk technicalspares groupservice co uk www vaillant co uk ...

Отзывы: