0020277262_02 ecoFIT sustain Installation and maintenance instructions
31
12 Inspection and maintenance
12.1
Complete Service Interval Record section
▶
After servicing, complete the relevant Service Interval
Record section of the Benchmark Checklist located on
the inside back pages of this document.
12.2
Using original seals
If you replace components, use only the enclosed original
seals; additional sealing materials are not required.
12.3
Observing inspection and maintenance
intervals
▶
Adhere to the minimum inspection and maintenance in-
tervals. The inspection may require maintenance to be
carried out earlier, depending on the results.
–
Inspection and maintenance work (
→
Appendix)
12.4
Checking the CO
₂
content
1.
Start up the product with check programme
(P.01)
.
Overview of the check programmes (
2.
Wait until the value that is read is stable.
–
Waiting period for reading a stable value: 5 min
1
3.
Unscrew the cover from the flue gas analysis point
(1)
.
4.
Measure the CO
₂
content at the flue gas analysis point
(1)
.
5.
Compare the measured value with the corresponding
value in the table.
Checking the CO
₂
content
Removed
front casing
Fitted front
casing
Natural gas H
Natural gas H
CO
₂
at full load
9.0
±
1.0 vol. %
9.2
±
1.0 vol. %
CO at full load
≤
250 ppm
≤
250 ppm
CO/CO
₂
≤
0.0031
≤
0.0031
◁
The value is OK.
▽
The value is not OK; you cannot start up the
product.
▶
Set the CO
₂
content. (
12.5
Setting the CO
₂
content
Condition
: CO
₂
content needs adjustment
1
A
B
▶
Remove the sticker.
▶
Turn the screw
(1)
to set the CO
₂
content (value with
front casing removed).
◁
To increase the CO
₂
content: Turn anti-clockwise
◁
To decrease the CO
₂
content: Turn clockwise
▶
Only carry out the adjustment in increments of 1/8 turn
and wait approximately 1 minute after each adjustment
until the value has stabilised.
▶
Compare the measured value with the corresponding
value in the table.
Setting the CO
₂
con-
tent
Removed
front casing
Fitted front
casing
Natural gas H
Natural gas H
CO
₂
at full load
9.0
±
0.2 vol. %
9.2
±
0.2 vol. %
Set for Wobbe index
W
₀
14.09 kW
⋅
h/m
³
14.09 kW
⋅
h/m
³
O
₂
at full load
4.5
±
1.8 vol. %
CO at full load
≤
250 ppm
≤
250 ppm
CO/CO
₂
≤
0.0028
≤
0.0028
▽
If the setting is not in the specified adjustment range,
you must not start up the product.
▶
Inform Customer Service.
▶
Check whether the air-quality requirements with regard
to carbon monoxide are fulfilled.
▶
Install the front panel.
12.6
Removing the gas-air mixture unit
Note
The gas-air mixture unit consists of three main
components:
–
Fan
–
Gas valve assembly
–
Burner hood
1.
Switch off the product via the main switch.
2.
Close the gas stopcock.
3.
Remove the front casing. (