Vageo VS-1 Скачать руководство пользователя страница 2

Features & Specifications

 

Location Imaging & controller 
settings

 

+05,0 

 C to +95,0 

 C in steps of 0,1 

 C

 

Differential Controller 

 

Adjustable -0,1 

 C to –25,0 

 C in steps of 0,1 

 C.

 

Setting Precision  
thermometer

 

Adjustable -3,0 

 C to +3,0 

 C in steps 0,1 

 C.

 

Dimensions

 

110 Χ 62 Χ 31mm 

Power supply 

 

~230V AC/50Hz ±10% 

Remote sensor

 

Extension to 50 meters (V-NTC50,V-NTC300 or V-NTCBOX)

 

Operating Temperature

 

-10,0

C to +50,0

C  

(TABLE 1) ! ATTENTION: The configuration process specific parameters should only be 
done by qualified personnel.

 

In standby <OFF> press continuously for three ( 3) seconds the button with the symbol       menu 
specific parameters and the yellow indicator lights up ( Figure 3 ) . 
► buttons with symbols             used for browsing the menu and change the price. 
► The button with the symbol       in the process of setting specific parameters works like                
< ENTRY > or <ENTER>. 
► Select the parameter with the arrow keys, press      , change the value again with the arrow keys 
and then press      . 
► To exit and save the parameter select End and press       .

 

Messages menu option

 

CAL 

± 3.0 

 C (factory setting 0 

 C).  

Calibration accuracy remote sensor.

 

dt 

Heating -0.1 

 C ..... -25.0 

 C (Factory setting -3.0 

 C) or C0.1 

 C ..... +25.0 

 C 

(Factory setting 3.0 

 C) Differential: negative or positive temperature variation from the 

desired temperature control means of sensing our.

 

Lo 

05.0 

 C ..... Hi (Factory setting 5.0 

 C). Setting lower limit value displayed temperature 

and control.

 

Hi 

Lo ..... 95.0 

 C (Factory setting 95.0 

 C). Setting price limits on the reported temperature 

& control.

 

C-H 

Option 

C

 Cool mode.  

Select 

H

Heat mode.  

(Factory setting 

H

Heat mode).

 

Por 

Select 

Off

 for state controller after power failure in the device.  

Select  

On 

for state controller after power failure in the device.  

(Factory setting 

Off

).

 

User Manual

VS-1

 

Products VAGEO HVAC 

designed and manufac-

tured in Greece by   

INTELCO Electronics 

PELEKIS & Co  

27 Christou Karvouni 

Str. Acharnes Attica   

GR 136 71 

T.+30 2102323345     
F.+30 2102386382      
[email protected]  

www.intelco.gr 

www.vageo.gr  

► The device is capable of calibration or correction of prices in degrees Celsius transducer <CAL>, 
Differential regulation desired <dt>, setting upper and lower limits <Hi> the <Lo> by the user. Finally 
controller mode setting after falling or power failure. To set the specific parameters consult  
(TABLE 1).

 

Digital Thermometer & Hydrostatic Multiple Applications for heating or cooling.

 

 
! CAUTION : Installing or uninstalling the device should only be done by a licensed electri-
cian or licensed Journeyman burner. If the product does not operate as specified by the 
manufacturer consult the service department of the manufacturer.

 

 

Installation: 

The VS-1 device always install the interior walls of the building at a height suitable 

for easy use. 
► pressing the hooks on the sides of the device (Figure 1 ) one at each side , remove the front 
thereof. Mark the hole locations , drill with drill diameter up to 5mm, then insert and align the bottom 
of the device by screwing the plugs the mounting screws (not included in package) . The cables 
must pass through the opening on the bottom of the device . 
► Connect the wires of the flow ( Figure 2 ) of heating or cooling to the appropriate connectors on 
the circuit board of the device and the remote sensor type 

V-NTC50, V-NTC300 or V-NTCBOX. 

 

! CAUTION : The cable attached to the sensor you suggest is shielded or be removed from 
power cords power devices power relay or power window relay .

 

► Snap the front panel of the base and feed the electricity 230V AC.

 

 
 
 
 
 
 
 

 
 

 

General Function: 

With the completion of the installation the device functions as a ther-

mometer. Pressing the <button ON / OFF>       (FIGURE 3) the device turn on or off the green ON 
indicator lights to go off, respectively. The setting temperature is with buttons            (FIGURE 3) and 
only when the device is in standby <ON>. During the process of setting switched on and off sequen-
tially yellow indicator <SET/MENU>. 
► For the control systems HEATING when setting the desired temperature is greater than dt ( de-
fault -3,0 C 

), the temperature of the application then check our device activates the relay system 

means that the testator . 
► For the control systems COOLING when setting the desired temperature is lower by dt ( default 
+3,0 C 

) the temperature of application then check our device activates the relay system means 

that the testator . In both cases the red indicator lights up with the symbol       ( Figure 3 ) .

 

Отзывы: