vacon • 8
Filter types
Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/
The VACON
®
NX AC drives comply with the immunity requirements EN/IEC 61800-3; 2004, second
environment as standard.
Note that the filters RFI-0012-5-IP54 to RFI-0105-5-IP54 are designed to fit mechanically directly to
the corresponding drive. All others are loose and must be connected to the drive separately.
2.1.2
RFI filter types
Table 1. RFI footprint filters for drive enclosure sizes 4-7
Suitability
Table 2. Drive suitability for 200 V AC and 500 V AC air-cooled drives, enclosure sizes 4-7
Installation
Figure 2. RFI filter installation principal diagram
Filter type code
Drawing
number
Manufacturer's
part code
Rated vol-
tage, 3~, 50-
60 Hz [V AC]
Nominal
current at
50°C [A]
Dimensions
W x H x D [mm]
W[kg]
IP
class
RFI-0012-5-IP54 70CTC1100857 FS32821-16-99
520
16
128 x 395 x 61.5
2.8
IP54
RFI-0031-5-IP54 70CTC1100865 FS32821-42-99
520
42
144 x 490 x 61.5
4.4
IP54
RFI-0061-5-IP54 70CTC1100869 FS32821-75-99
520
75
195 x 625 x 90
8.2
IP54
RFI-0105-5-IP54 70CTC1100887 FS32821-130-99
520
130
230 x 745 x 100
15.5
IP54
200 V AC drive
Filter
500 V AC drive
Filter
NX_0003-0012 2
RFI-0012-5-IP54
NX_0003-0012 5
RFI-0012-5-IP54
NX_0017-0031 2
RFI-0031-5-IP54
NX_0016-0031 5
RFI-0031-5-IP54
NX_0048-0061 2
RFI-0061-5-IP54
NX_0038-0061 5
RFI-0061-5-IP54
NX_0075-0088 2
RFI-0105-5-IP54
NX_0072-0105 5
RFI-0105-5-IP54
#
Reference
#
Reference
A
Keypad
C
Power unit
B
Control
D
RFI filter
7119_00
A
B
C
D
L1
L2
L3
U/T1
V/T2
W/T3
D
C
-
D
C
+
/R
-
R
-
Содержание RFI-0012-5-IP54
Страница 1: ...vacon nx ac drives rfi du dt and sine filters user manual...
Страница 2: ......