FAULT TRACING
vacon • 97
11.
FAULT TRACING
The fault codes, their causes and correcting actions are presented in Table 11-2 below. The
converter has an internal memory for storing the converter status at the time of fault as well as
additional information about the source of the fault. This feature is intended to help the user or the
service personnel to determine the cause of fault.
11.1 Fault time data record
When a fault occurs a fault code is displayed on the keypad. By pushing the
Menu button right
here
you will enter the
Fault time data record menu
indicated by T.1 T.16. In this menu, some selected
important data valid at the time of the fault are recorded.
T.1
Operation days
D
T.2
Operation hours
hh:mm:ss
T.3
Output frequency
Hz
T.4
Motor current
A
T.5
Motor voltage
V
T.6
Motor power
%
T.7
Motor torque
%
T.8
DC voltage
V
T.9
Unit temperature
C
T.10
Run status
T.11
Direction
T.12
Warnings
T.13
0-speed*
T.14
Subcode.
Contains more specific information about the fault.
S1…S#:
System generated fault. See fault table below.
A1:
Application generated fault. See table below or application-
specific documentation.
T.15
Module code.
Indicates where the fault was detected.
Power:
Power unit of the converter (sizes up to FR11)
Power1:
First power unit in a parallel converter (e.g. in FR12)
Power2:
Second power unit in a parallel converter (e.g. in FR12)
Control:
Control part or control part communication
Expander:
Expander board or expander board communication
Adapter:
Adapter board or adapter board communication
Starcoupler: Starcoupler board (parallel unit only, e.g. FR12)
Motor:
Motor-related problem
Software:
Application software
T.16
Module subcode.
Indicates the source for the problem within the Module indicated in T.15.
Unit:
Cause of problem in unit, not specified
Board:
Problem in PCB or communication with PCB
U-Phase:
Fault origin in the U-phase
V-Phase:
Fault origin in the V-phase
W-Phase:
Fault origin in the W-phase
Slot A-E:
Fault origin in the slot indicated by A, B, C, D or E
Application: Fault in application
Table 11-1. Fault time recorded data
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred