Ventilation

vacon • 7

Local contacts: https://www.danfoss.com/en/contact-us/contacts-list/

2

2.2

Arranging ventilation of the enclosure

CAUTION! 

It is of utmost importance for the operation and lifetime of the frequency converter that 

the closure is well ventilated to keep the temperature below the maximum operating temperature. 
Repeated overheating will shorten the lifetime of the converter.

Table 1. Ventilation requirements table

Minimum air hole on switchgear/dm

2

Frame

Cooling air 

required m

3

/h

1) Inlet

2) Outlet

FR9

1300

9.1

7

FR10

2000

9.5

5

FR11

3000

14

7.5

FI9

1150

5.5

3

FI10

1400

6.5

4

FI12

2800

13

7

FI13

4200

19.5

10.5

1

2

12023A_00

Содержание NXP series

Страница 1: ...installation quick guide frames fr9 to fr14 ip00 modules ac drives vacon nxp...

Страница 2: ......

Страница 3: ...kes and power module 4 1 1 Products included in the delivery 4 1 2 Lifting the power module 4 1 3 Installing the power module 5 2 Ventilation 6 2 1 Steering the internal air flow 6 2 2 Arranging venti...

Страница 4: ...2 2 x FR10 FI14 2 x FI13 power modules NOTE In FR9 the AC choke is inside the power module 1 2 Lifting the power module NOTE Place the lifting hooks symmetrically in at least two holes The lifting dev...

Страница 5: ...ist 1 1 3 Installing the power module NOTE For detailed drawing see manual Frame Device width A mm Supporting bar range B mm Recommended cabinet width C mm FR9 480 A 50 mm 600 FR10 500 A 50 mm 600 FR1...

Страница 6: ...s https www danfoss com en contact us contacts list 2 VENTILATION 2 1 Steering the internal air flow NOTE Outgoing air must be directed out of the cabinet so that it does not mix with incoming cooling...

Страница 7: ...ter that the closure is well ventilated to keep the temperature below the maximum operating temperature Repeated overheating will shorten the lifetime of the converter Table 1 Ventilation requirements...

Страница 8: ...www danfoss com en contact us contacts list 3 GROUNDING AND CABLING THE UNIT 3 1 Connecting the internal power cable See IP00 Module Installation Manual for details NOTE No external choke in FR9 FI F...

Страница 9: ...on 9 Local contacts https www danfoss com en contact us contacts list 3 3 2 Installing the optical fibers 3 3 Installing the motor cable Min bending radius X2 X1 1 2 3 4 5 6 7 12025A_uk Cable fixing c...

Страница 10: ...Document ID DPD00889B Rev B Vacon Ltd Member of the Danfoss Group Runsorintie 7 65380 Vaasa Finland www danfoss com...

Отзывы: