INSTALLATION INSTRUCTIONS
vacon • 67
24-hour s358 (0)201 212 575 • Email: [email protected]
8
8.3
Connecting power supply and internal control cables
You might need to establish the fibre cable connections from the star coupler board to the power
module. Connect the cables according to Figure 41.
The control unit uses 24 VDC supplied from the ASIC board, which is located on the left side of the
power unit 1. To access the board, remove the protective cover in front of the power module.
Connect the power supply cable to the X10 connector on the ASIC board and to the X2 connector on
the rear side of the control unit.
Figure 40. Connecting the power supply and control cables to the control unit, FR12
Each fibre optic cable has a number 1...8 and 11…18 marked on the cable shield at both cable ends.
Connect each cable to the connectors marked with the same number on the ASIC board and on the
rear side of the control unit. Additionally, you may have to connect the 4 fibre cables from the
feedback board to the star coupler board. The list of the optic signals can be found in Chapter 8.4.
Fix the cable bundle at two or more points, at least one at each end, to prevent damages to the
cables.
Fasten the protective cover on the power unit when the work is finished.
CAUTION!
Be careful when connecting the fibre optic cables! Connecting the wires
incorrectly will damage power electronic components.
NOTE!
The minimum bending radius for optical cables is 50 mm.
X10
Power module 1
ASIC board
Power module 2
ASIC board
FB board
X2
Min bending radius 50 mm
Star coupler board