6
vacon • 48
CABLING AND CONNECTIONS
Tel. +358 (0) 201 2121 • Fax +358 (0)201 212 205
6.2.7
Cable and fuse sizes, 500/525-690 V units
The table below shows typical cable sizes and types that can be used with the converter.
The final selection should be done according to local regulations, cable installation conditions and
cable specification.
6.2.7.1
6-pulse drives
Table 16. Cable and aR fuse sizes for Vacon NX_6, 6-pulse supply
Frame
Type
I
L
[A]
Bussmann/
Ferraz Shawmut fuse
type
Fuse I
n
[A]
Mains and motor
cable
1)
[mm
2
]
No of
supply
cables
No of
motor
cables
FR9
NXC0125 6
NXC0144 6
NXC0170 6
NXC0208 6
125
144
170
170M3819 (3 pcs)
NH1UD69V400PV (3 pcs)
400
Cu: 3*95+50
Even/Odd
Even/Odd
208
170M3819 (3 pcs)
NH1UD69V400PV (3 pcs)
400
Cu: 3*150+70
Even/Odd
Even/Odd
FR10
NXC0261 6
261
170M5813 (3 pcs)
NH2UD69V700PV (3 pcs)
700
Cu: 3*185+95
Al: 2*(3*95Al+29Cu)
Even/Odd
Even/Odd
NXC0325 6
325
170M5813 (3 pcs)
NH2UD69V700PV (3 pcs)
700
Cu: 2*(3*95+50)
Al: 2*(3*150Al+41Cu)
Even/Odd
Even/Odd
NXC0385 6
385
170M5813 (3 pcs)
NH2UD69V700PV (3 pcs)
700
Cu: 2*(3*120+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
NXC0416 6
416
170M5813 (3 pcs)
NH2UD69V700PV (3 pcs)
700
Cu: 2*(3*150+70)
Al: 2*(3*185Al+57Cu)
Even/Odd
Even/Odd
FR11
NXC0460 6
460
170M8547 (3 pcs)
NH3UD69V1000PV (3 pcs)
1250
Cu: 2*(3*150+70)
Al: 2*(3*240Al+72Cu)
Even/Odd
Even/Odd
NXC0502 6
502
170M8547 (3 pcs)
NH3UD69V1000PV (3 pcs)
1250
Cu: 2*(3*185+95)
Al: 2*(3*300Al+88 Cu)
Even/Odd
Even/Odd
NXC0590 6
590
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 2*(3*240+120)
Al: 4*(3*120Al+41Cu)
Even
Even/Odd
FR12
NXC0650 6
650
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 4*(3*95+50)
Al: 4*(3*150Al+41Cu)
Even
Even
NXC0750 6
750
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 4*(3*120+70)
Al: 4*(3*150Al+41Cu)
Even
Even
NXC0820 6
820
170M5813 (6 pcs)
NH2UD69V700PV (6 pcs)
700
Cu: 4*(3*150+70)
Al: 4*(3*185Al+57Cu)
Even
Even
FR13
NXC0920 6
920
No additional drive fuses needed
Cu:4*(3*150+70)
Al:4*(3*2405+72Cu)
Even/Odd
Even/Odd
NXC1030 6
1030
No additional drive fuses needed
Cu:4*(3*185+95)
Al:5*(3*185+57Cu)
Even/Odd
Even/Odd
NXC1180 6
1180
No additional drive fuses needed
Cu:5*(3*185+95)
Al:6*(3*185+72Cu)
Even/Odd
Even/Odd
FR14
NXC1500 6
1500
No additional drive fuses needed
Cu:6*(3*185+95)
Al:8*(3*185+57Cu)
Even/Odd
Even
NXC1900 6
1900
No additional drive fuses needed
Cu:6*(3*240+120)
Al:8*(3*240+72Cu)
Even
Even
NXC2250 6
2250
No additional drive fuses needed
Cu:8*(3*240+120)
Al:8*(3*300+88Cu)
Even
Even
1)
Based on correction factor 0.7. Cables are laid on a cable ladder side by side, three ladders on top of each
other. Ambient temperature is 30 °C (86 °F). EN60204-1 and IEC 60364-5-523.