TECHNICAL DATA
vacon • 15
24-hour s358 (0)201 212 575 • Email: [email protected]
4
4.
TECHNICAL DATA
4.1
Power ratings
4.1.1
Vacon NXC – Mains voltage 380-500 V
NOTE!
The rated currents in given ambient temperatures are achieved only when the switching
frequency is equal to or less than the factory default (automatic thermal management).
*The dimensions indicated are for the basic 6-pulse IP21 version of the converter cabinet. Some
options may increase the width, height or weight of the cabinet. See the delivery specific
documentation for more details.
High overload = Max current I
S
, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload
current for 1 min, followed by a period of load current less than rated
current, and of such duration that the r.m.s output current, over the duty
cycle, does not exceed rated output current (IH)
Low overload = Max current I
S
, 2 sec/20 sec, Rated overload current, 1 min/10 min
Following continuous operation at rated output current, rated overload
current for 1 min, followed by a period of load current less than rated
current, and of such duration that the r.m.s output current, over the duty
cycle, does not exceed rated output current (IL)
Table 2. Power ratings and dimensions of Vacon NX 6- and 12-pulse drives supply voltage 380-500V
Mains voltage 380-500 V, 50/60 Hz, 3~
Frequency
converter
type
Loadability
Motor shaft power
Frame
Dimensions and weight*
WxHxD/kg
Low
High
400V supply
500V supply
Rated
contin.
current
I
L
(A)
Rated
overload
current
(A)
Rated
contin.
current
I
H
(A)
Rated
over-
load
current
(A)
Max
current
I
S
Low
over-
load
P(kW)
High
over-
load
P(kW)
Low
over-
load
P(kW)
High
over-
load
P(kW)
NXC0261 5
261
287
205
308
349
132
110
160
132
FR9
606x2275x605/371
NXC0300 5
300
330
245
368
444
160
132
200
160
FR9
606x2275x605/371
NXC0385 5
385
424
300
450
540
200
160
250
200
FR10
606x2275x605/371
NXC0460 5
460
506
385
578
693
250
200
315
250
FR10
606x2275x605/403
NXC0520 5
520
572
460
690
828
250
250
355
315
FR10
606x2275x605/403
NXC0590 5
590
649
520
780
936
315
250
400
355
FR11
806x2275x605/577
NXC0650 5
650
715
590
885
1062
355
315
450
400
FR11
806x2275x605/577
NXC0730 5
730
803
650
975
1170
400
355
500
450
FR11
806x2275x605/577
NXC0820 5
820
902
730
1095
1314
450
400
560
500
FR12
1206x2275x605/810
NXC0920 5
920
1012
820
1230
1476
500
450
630
560
FR12
1206x2275x605/810
NXC1030 5
1030
1133
920
1380
1656
560
500
710
630
FR12
1206x2275x605/810
NXC1150 5
1150
1265
1030
1545
1620
630
560
800
710
FR13
1406X2275X605/1000
NXC1300 5
1300
1430
1150
1725
2079
710
630
900
800
FR13
6-p: 1606X2275X605/1150
12-p: 2006X2275X605/1150
NXC1450 5
1450
1595
1300
1950
2484
800
710
1000
900
FR13
6-p: 1606X2275X605/1150
12-p: 2006X2275X605/1150
NXC1770 5
1770
1947
1600
2400
2880
1000
900
1200
1100
FR14
2806X2275X605/2440
NXC2150 5
2150
2365
1940
2910
3492
1200
1100
1500
1300
FR14
2806X2275X605/2500
Содержание nxp/c
Страница 1: ...vacon nxp c ac drives user manual ...
Страница 2: ......
Страница 110: ......
Страница 111: ......