90 • vacon
board opt-ai
Telephone: +358-201-2121 • Fax: +358-201-212 205
11
10.
DESCRIPTION OF EXPANDER BOARD OPT-AA
Description: I/O expander board with one relay output, one open collector output
and three digital inputs.
Allowed slots:
Vacon NXL board slot E
Type ID:
16705
Terminals:
Two terminal blocks; Screw terminals (M2.6 and M3); No coding
Jumpers: None
Board parameters:
None
I/O terminals on OPT-AA
Terminal
Parameter
setting
Description
X3
1
+24V
Control voltage output; voltage for switches etc, max. 150 mA
2
GND
Ground for controls, e.g for +24 V and DO
3
DIN1
DIGIN:x.1
Digital input 1
4
DIN2
DIGIN:x.2
Digital input 2
5
DIN3
DIGIN:x.3
Digital input 3
6
DO1
DIOUT:x.1
Open collector output, 50mA/48V
X5
24 RO1/NC DIOUT:x.2
25 RO1/C
26 RO1/NO
Relay output 1 (NO)
Switching capacity:
24VDC/8A
250VAC/8A
125VDC/0,4A
Table 10-1. I/O terminals of board OPT-AA
Note! The +24 V control voltage terminal can also be used to power the control module (but not the
power module).