control keypad
vacon • 79
24-hour support: +358-(0)40-
8371 150 • Email: [email protected]
7
System menu functions
Code
Function
Min
Max
Unit
Default
Cust
Selections
S6.1
Selection of
language
English
English
Deutsch
Suomi
Svenska
Italiano
S6.2
Application selection
Basic
Application
Basic Application
Standard Application
Local/Remote control Appl.
Multi-Step Application
PID Control Application
Multi-Purpose Control Appl.
Pump and Fan Control Appl.
S6.3
Copy parameters
S6.3.1
Parameter sets
Load factory defaults
Store set 1
Load set 1
Store set 2
Load set 2
S6.3.2
Load to keypad
All parameters
S6.3.3
Load from keypad
All parameters
All but motor parameters
Application parameters
P6.3.4
Parameter backup
Yes
No
Yes
S6.4
Parameter
comparison
S6.5
Safety
S6.5.1
Password
Not used
0=Not used
P6.5.2
Parameter locking
Change
Enabled
Change Enabled
Change Disabled
S6.5.3
Start-up wizard
No
Yes
S6.5.4
Multimonitoring
items
Change
Enabled
Change Enabled
Change Disabled
S6.6
Keypad settings
P6.6.1
Default page
P6.6.2
Default page/OM
P6.6.3
Timeout time
0
65535
s
30
P6.6.4
Contrast
0
31
18
P6.6.5
Backlight time
Always
65535
min
10
S6.7
Hardware settings
P6.7.1
Internal brake
resistor
Connected
Not connected
Connected
P6.7.2
Fan control function
Continuous
Continuous
Temperature
P6.7.3
HMI acknowledg.
200
5000
ms
200
P6.7.4
HMI: no. of retries
1
10
5
S6.8
System information
S6.8.1
Total counters
C6.8.10.1.
MWh counter
kWh
C6.8.10.2.
Operation day
counter
C6.8.1.3.
Operation hour
counter
S6.8.2
Trip counters
T6.8.2.1
MWh counter
kWh
T6.8.2.2
Clear MWh counter
Содержание NXI
Страница 1: ...vacon nxi inverters fi9 fi14 user manual ...
Страница 24: ...24 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 2 Vacon NXI dimensions FI10 ...
Страница 26: ...26 vacon installation Tel 358 201 2121 Fax 358 201 212 205 5 Figure 5 4 Vacon NXI dimensions FI12 front view ...
Страница 104: ......