AT LEAST THE 10 FOLLOWING STEPS OF THE
START-UP QUICK GUIDE
MUST BE PERFORMED DURING
THE INSTALLATION AND COMMISSIONING.
IF ANY PROBLEMS OCCUR, PLEASE CONTACT YOUR LOCAL DISTRIBUTOR.
Start-up Quick Guide
1.
Check that the delivery corresponds to your order, see Chapter
3.
2.
Before taking any commissioning actions, read carefully the safety instructions in
Chapter 1.
3.
Before the mechanical installation, check the minimum clearances around the unit and
check the ambient conditions in Chapter
5.
4.
Check the size of the motor cable, DC supply cable, and mains fuses, and check the
cable connections. Read Chapters
6.1.1.1 –
6.1.1.6.
5.
Follow the installation instructions, see Chapter
6.1.2.
6.
The sizes and earthing of control connections are explained in Chapter
6.2.1.
7.
If the Start-Up wizard is active, select the language you want the keypad and the
application to use and confirm by pressing the
enter
button. If the Start-Up wizard is not
active, follow the instructions in 7a and 7b below.
7a. Select the language of the keypad from Menu M6, page 6.1. Instructions on using the
keypad are given in Chapter
7.
7b. Select the application you want to use from Menu M6, page 6.2. Instructions on using
the keypad are given in Chapter
7.
8.
All parameters have factory default values. To ensure proper operation, check the rating
plate data for the values below and the corresponding parameters of parameter group
G2.1.
nominal voltage of the motor
nominal frequency of the motor
nominal speed of the motor
nominal current of the motor
motor cos
All parameters are explained in the All in One Application Manual.
9.
Follow the commissioning instructions, see Chapter
8.
10.
The Vacon NX Inverter is now ready for use.
Vacon Plc is not responsible for the use of the inverters against the instructions.